www.enviromaster.com
WLCA/WLHA High Wall Evaporator
14
rEfriGErAnt proCEssinG
WLC/WLH HiGH WALL EVAporAtor instALLAtion instrUCtions
s2C rEfriGErAnt CHArGE tABLE
Condenser
Evaporator pairing
Line Chg/ft
factory Charge
S2C99
WLH09
.25 oz.
28 oz./ 28 oz.
S2C22
WLH12
.25 oz.
33 oz./ 33 oz.
S2C92
WLH09+WLH12
.25 oz.
28 oz./ 33 oz.
s1C rEfriGErAnt CHArGE tABLE
Condenser
Evaporator pairing
Line Chg/ft
factory Charge
S1C9
WLH09
.25 oz.
37 oz.
S1C2
WLH12
.25 oz.
40 oz.
S1C8
WLH24
.56 oz.
51 oz.
S1C4
WLH24
.56 oz.
65 oz.
S1C3
WLC30
.56 oz.
72 oz.
S1C6
WLC36
.56 oz.
90 oz.
s1H (HEAt pUmp) rEfriGErAnt CHArGE tABLE
Condenser
Evaporator pairing
Line Chg/ft
factory Charge
S1H9
WLH09
.25 oz.
41 oz.
S1H2
WLH12
.25 oz.
44 oz.
S1H8
WLH24
.56 oz.
53 oz.
S1H4
WLH24
.56 oz.
67 oz.
8. Charge to proper weight, charge
based on your feet of interconnect
(see below).
Note:
Charging should be done with a
dial-a-charge or weighed in with a scale.
Refrigerant
R-22
refer to refrigerant
Charge table for
specified line charge.
Top discharge
condeser shown
top disCHArGE rEfriGErAnt CHArGE CHArt
Circuit Capacity
Line Chg/ft
factory Charge
ref.
09
.25 oz.
28 oz.
R-22
12
.25 oz.
30 oz.
R-22
18
.56 oz.
48 oz.
R-22
24
.56 oz.
60 oz.
R-22
IMPORTANT NOTES:
I. To find the charge adjustment and system charge for any evaporator and tubing length:
Line Adjustment = (Line Chg/Ft) x Line Length
System Total = Factory Line Adjustment
2. Round to the nearest ounce and allow for gauges and hoses.
3. Use R22 refrigerant.
Summary of Contents for AmericaSeries WLC30