23
Connection to spring-loaded terminals
Proceed as follows to connect external devices to the spring-loaded
terminals:
1. Shorten the conductors to the necessary length.
2. Strip 4 to 5 mm of the conductor.
3.
If it is a finely stranded conductor, equip it with a ferrule. Ensure
that all individual wires are fully inside the terminal.
4. Push the lever of the spring-loaded terminal
down with the screwdriver until the terminal
opens.
5. Insert the line into the open terminal up to its
insulation. Ensure that the cable insulation is
not put inside the terminal.
6. Remove the screwdriver to allow the
terminal to close.
7. Repeat the process until all conductors are connected.
Securing the terminal cover
To prevent any unauthorised access to the connection terminals, the
terminal cover is attached with 2 sealing screws (slot and PZ2 drive),
which you can secure with seals.
ATTENTION
Application of excessive torque will damage the device!
y
Tighten the sealing screws on the terminal cover with a maximum
torque of 0.5 Nm.