With additional tools, the technician can find out more about the system guided by the following
table :
Discharge
Discharge
Suction
Superheat SubCooling Amperage
Pressure Temperature Pressure
Draw
Refrigerant Overcharge
High
Low
High
Low
High
High
Refrigerant Undercharge
Low
High
Low
High
Low
Low
Restriction at the Filter Drier
Low
High
Low
High
High
Low
Low Evaporator Airflow
Low
Low
Low
Low
High
Low
Blocked or Dirty Condensor Coil
High
High
High
Low
Low
High
TXV with lost bulb charge
Low
Low
Low
High
High
Low
High Evaporator Airflow
High
High
High
High
Low
High
Dragging or Seizing Compressor
Low
High
High
High
High
High
Electrical Phase Imbalance
Low
High
High
High
High
Low
Non-Condensibles in system
High
High
High
High
Low
High
High : Higher than Normal
Low : Lower than Normal