7.0 Essential Service/Installation Tools, Equipment and
Materials
Before attempting the Start-Up process , the technician needs to assemble the correct tools and
equipment for the task. Apart from the normal refrigeration service technician tools, electrical test
equipment and hand tools, the following items are essential for the installation of hermetic
refrigeration systems :
Vacuum Pump
of sufficient size for the total refrigeration system and capable of
pulling a vacuum of at least 100 microns. This pump should be fitted with a proper
vacuum breaker valve in event of this pump loses power supply during the evacuation
process
A Four Port Charging Manifold
including;(1) A 3/8” hose to vacuum pump, (2) All
hoses fitted with removable schraeder depressors, (3) One compound and one
pressure gauge. All of this equipment to be leak free, accurate and reliable. (See Fig
14 below)
Fig 14 . Four Port Charging Manifold
Clean and new (not recycled)
R22 Refrigerant
of sufficient quantity for the refrigerant
operating
change plus leak testing. Note: Refrigerant cylinders must be of the type that
can deliver liquid refrigerant until empty.
Oxygen-free
Nitrogen
and regulators.
Reliable Electronic Vacuum Gauge
. A clean and leak free refrigeration system can
only be assured if the initial vacuum is deep and holds on test. This equipment must
read to the standards indicated in the recommended start-up procedures (Section 10.)
23
Summary of Contents for ZX
Page 8: ...Fig 4 The Defrost Module Fig 5 The Diagnostic Module now available without Buzzer 8 ...
Page 21: ...ZX200 300 400 Single Fan Units 21 ...
Page 22: ...ZX500 600 750 Dual Fan Units 22 ...
Page 43: ...Fig 23 Diagnostic Module and Defrost Module connected to the E2 Unit Controller 43 ...
Page 51: ...Addendum 17 2 ZX Wiring Diagram 51 ...
Page 52: ...Addendum 17 3 Capacity kW at 50Hz for Refrigerant R22 52 ...
Page 54: ...54 ...