This work should Only be carried out by Suitably Qualified Electrical Technicians.
Please check the unit nameplate and run ample capacity three phase and single phase (including
neutral and earth wiring) to each unit. A suitably rated
Isolating Switch
( this is also an Option
that could be selected ) should be fitted immediately adjacent to each unit .This is not only good
practice from a safety standpoint, but is usually a mandatory requirement for most electrical
supply authorities today.
All incoming phase lines are to be
suitably fused
at the Sub-Board to protect the installed wiring
and the unit.
9.0 Refrigeration Piping Installation
This work should Only be carried out by Suitably Qualified Refrigeration Technicians.
A good understanding of modern, Scroll Compressor Hermetic Systems is also essential when
carrying out this work-in particular, the importance of initial evacuation and charging procedures.
All interconnecting piping should be of refrigeration grade, clean, dehydrated and
remain capped at both ends until installation. Even during installation, if the system is
left for any reasonable period of time (say 2 hours), pipes should be re-capped to
prevent moisture and contaminant from entering the system.
It is advisable to insulate both the suction and liquid interconnecting piping between the ZX unit
and the evaporator. Usually the suction line is insulated, but the liquid line is not. However the
liquid line can pick up additional heat from the ambient and adversely affect the sub-cooling
desirable for the liquid refrigerant before it enters the expansion valve.
Pipe sizing should not only the sufficient size to ensure optimum performance and good oil return
but it also needs to take into account the full capacity range through which this particular unit will
need to operate.
Pipe runs should be kept as short as possible, using the minimum number of directional changes.
Use large radius bends and avoid trapping of oil and refrigerant. This is particularly important for
the suction line. The suction line should ideally slope gently toward the unit. Recommendation
25
Summary of Contents for ZX
Page 8: ...Fig 4 The Defrost Module Fig 5 The Diagnostic Module now available without Buzzer 8 ...
Page 21: ...ZX200 300 400 Single Fan Units 21 ...
Page 22: ...ZX500 600 750 Dual Fan Units 22 ...
Page 43: ...Fig 23 Diagnostic Module and Defrost Module connected to the E2 Unit Controller 43 ...
Page 51: ...Addendum 17 2 ZX Wiring Diagram 51 ...
Page 52: ...Addendum 17 3 Capacity kW at 50Hz for Refrigerant R22 52 ...
Page 54: ...54 ...