7.2  EMERSON ECP-024 CONNECTION 

The Emerson ECP-024 rechargeable accumulator can be connected to the XM678D  
to close the stepper valve in case of power interruption. 
 

Wiring connection 

XM678D 

ECP-024 

Terminal 61 (+) 

Te 

Terminal 62 (-) 

Terminal - 

 
About conditions of use and limitation please refer to the ECP-024 manuals. 
 

8.  USER INTERFACE 

8.1  DIRECT COMMAND INTERFACE 

 

8.2  ICONS 

Cooling output 

 

     ↓ 

With icon ON the output 
is  active,  while  with 
blinking  icon  there  is  a 
delay. 
 

MEASUREMENT UNIT 

°C,  Bar 

and

 

  (time)

 

are

 

ON  depending  on 

the selection. 

Light  

  

 

 

 

← Fan 

Defrost  → 

 

AUX

 

←  Auxiliary relay 

Energy saving  

→ 

 

 

←  Multimaster 
Enabled 

Generic alarm 

→ 

 

 

←  Clock / time 

DURING PROGRAMMING

:  blink the measurement units of temperature and 

pressure 

8.3  KEYBOARD COMMANDS 

Single commands: 

LIGHT relay 

Press light button.

 

AUX relay 

Press down arrow.

 

Manual defrost 

Press and hold for 3 sec the defrost button

 

ON/OFF 

Press  for  3  sec  the 

ON/OFF

  button  (if  the  function  is 

enabled).

 

Energy Saving 

Press  for  3  sec  the 

ON/OFF

  button  (if  the  function  is 

enabled).

 

 
Double commands: 

 

Press and hold for about 3 sec to lock (

Pon

) or unlock (

PoF

) the 

keyboard. 

 

Pressed together to exit from programming mode or from menu; on 
submenus 

rtC

 and 

EEV

 this combination allow to come back to 

previous level. 

 

Pressed together for 3 sec allow to access to first level of 
programming mode. 

8.4  HOW  TO  MODIFY  THE  SET  POINT  FOR  AIR  TEMPERATURE 
REGULATION 

The thermostat set point is the value that will be used to regulate the air temperature. 
The regulation output is controlled by the electronic valve or by the relay. 
 

BEGIN 

 

Press SET button for 3 sec, the measurement units 
will blink together.  

Value 

modification 

 or 

 

With  the  arrows  it’s  possible  to  change  the  value 
within the LS and US parameters value. 

EXIT 

 

By  pressing  SET  it  is  possible  to  confirm  the  value 
that will blink for about 2 sec. 

 
In  any  case,  it  is  possible  to  wait  for  about  10  sec  to  exit.  In  order  to  show  the  air 
temperature set is sufficient to press and release the SET button, the value is displayed 
for about 60 sec. 

9.  HOW  TO  PROGRAM  THE  PARAMETERS  (PR1  AND 
PR2) 

The device provide 2 programming levels: 

Pr1

 with direct access and 

Pr2

 protected 

with a password (intended for experts). 
 

ACCESS 
to Pr1 

 

Press and hold for about 3 sec to have access to 
the first programming level (

Pr1

).  

Select 
item 

 or 

 

Select the parameter or submenu using the 
arrows. 

Show 
value 

 

Press 

SET 

button. 

Modify 

 or 

 

Use the arrows to modify the value. 

Confirm 
and store 

 

Press 

SET 

key: the value will blink for 3 sec, and 

then the display will show the next parameter. 

EXIT 

 

Instantaneous  exit  from  the  programming  mode, 
otherwise wait for about 10 sec (without press any 
button). 

9.1  HOW TO HAVE ACCESS TO “PR2” 

To enter 

Pr2

 programming menu: 

1. Access to a 

Pr1

 menu by pressing both 

SET+DOWN 

keys for 3 sec, the first 

parameter label will be showed; 

2. Press 

DOWN 

key till the 

Pr2

 label will be showed, then press 

SET

3. The blinking 

PAS

 label will be showed, wait some seconds; 

4. Will be showed “

0 - -

” with blinking 0: insert the password [

321

] using the keys 

UP

 and 

DOWN 

and confirming with 

SET

 key. 

GENERAL STRUCTURE: 

The first two item 

rtC

 and 

EEV

 are related to submenus 

with others parameters. 

 

 

SET+UP

 keys on 

rtC

 or 

EEV

 submenus allow coming back to parameter list, 

 

SET+UP

  keys on parameter list allow immediate exit. 

9.2  HOW  TO  MOVE  PARAMETER  FROM  PR1  TO  PR2  AND  VICE 
VERSA 

Enter on 

Pr2

; select the parameter; press together [

SET

 + 

DOWN

]; a left side LED ON 

gives to the parameter the presence on 

Pr1

 level, a left side LED OFF means that the 

parameter is not present on 

Pr1

 (only 

Pr2

). 

10.  FAST ACCESS MENU 

This menu contains the list of probes and some values that are automatically evacuate 
by the board such as the superheat and the percentage of valve opening. The values: 

nP

 or 

noP

 stands for probe not present or value not evacuate, 

Err

 value out of range, 

probe damaged not connected or incorrectly configured. 
 

Entering 

fast 

access 

menu 

 

By press and release the 

UP arrow

. The duration 

of the menu in case of inactivity is about 3 min. 
The values that will be showed depend on the 
configuration of the board. 

Summary of Contents for XM678D

Page 1: ... that permits to be programmed in a simple way The optional direct serial output RS485 ModBUS compatible permits a simple XWEB interfacing RTC is available as options The HOT KEY connector can be used to connect X REP display Depending on the model 4 QUICK REFERENCE GUIDE HOW TO RUN THE SELF ADAPTIVE REGULATION IN 5 STEPS 1 After wiring the XM678D configure the type of valve bipolar or unipolar vi...

Page 2: ... wrong settings tEP Model LSt steps 10 uSt steps 10 CPP mA 10 CHd mA 10 Sr step s tEu bip unip HSF Half full 0 Manual settings Par Par Par Par Par Par Par 1 Danfoss ETS 25 50 7 262 10 10 300 bP FUL 2 Danfoss ETS 100 10 353 10 10 300 bP FUL tEP Model LSt steps 10 uSt steps 10 CPP mA 10 CHd mA 10 Sr step s tEu bip unip HSF Half full 3 Danfoss ETS 250 400 11 381 10 10 300 bP FUL 4 Sporlan SEI 5 to 11...

Page 3: ...the bounds of the pressure transducer or the P5C parameter is wrong Check all these options and eventually change the transducer rPF the remote pressure transducer is on error situation Check the status of the onboard GREEN LED if this LED is OFF the LAN is not working otherwise check the remote transducer LAST CHECKS ABOUT SUPERHEAT On the fast access menu dPP is the value read by the pressure ga...

Page 4: ...ow the air temperature set is sufficient to press and release the SET button the value is displayed for about 60 sec 9 HOW TO PROGRAM THE PARAMETERS PR1 AND PR2 The device provide 2 programming levels Pr1 with direct access and Pr2 protected with a password intended for experts ACCESS to Pr1 Press and hold for about 3 sec to have access to the first programming level Pr1 Select item or Select the ...

Page 5: ...can perform simultaneous defrosts with the possibility to end them in a synchronized way The Adr parameter cannot be duplicated because in this case the defrost cannot be correctly managed BEGIN Press for 3 seconds the rtC or other will be showed The measurement unit blinks Find Adr Press more than once the DOWN arrow to find the Adr parameter the press SET Modify Adr or Set the value of Adr param...

Page 6: ...h racks Sub 5 13 2 GENERAL CONSIDERATIONS The controller is able to regulate the superheat in manual or self adaptive mode according to the value of the parameter AMS autotuing enabling With AMS n the normal SH regulation is performed With AMS y the self adaptive SH regulation is performed 13 3 MANUAL OPERATING MODE AMS NO The temperature and SH regulation can be performed in 2 ways according to t...

Page 7: ... physical probe or virtual probe obtained by a weighted average between two probes following the formula value_for_room_regulation rPA rPE rPb 100 rPE 100 If the temperature increases and reaches set point plus differential the solenoid valve is opened and then it is closed when the temperature reaches the set point value again In case of fault in the thermostat probe the opening and closing time ...

Page 8: ...o that the relay will be ON for AMt minutes and OFF for 60 AMt minutes In case of P4 error or if P4 is absent the output is at AMA value for the AMt time then the output is at 0 value for the time 255 AMt time performing a simple PWM modulation 16 6 AUXILIARY OUTPUT The auxiliary output is switch ON and OFF by means of the corresponding digital input or by pressing and releasing the down arrow key...

Page 9: ...0 during workdays nU not used Format hours 10min resolution 10min Ld2 13 0 Workdays Second defrost start Ld1 to 23h50min 143 nU 144 Ld3 21 0 Workdays Third defrost start Ld2 to 23h50min 143 nU 144 Ld4 nU Workdays Fourth defrost start Ld3 to 23h50min 143 nU 144 Ld5 nU Workdays Fifth defrost start Ld4 to 23h50min 143 nU 144 Ld6 nU Workdays Sixth defrost start Ld5 to 23h50min 143 nU 144 Sd1 6 0 Holid...

Page 10: ...pening valve percentage during hot gas defrost During hot gs defrost there is not SH control MnF 100 Maximum percentage of opening admitted during normal functioning 0 to 100 During regulation it sets the maximum valve opening percentage This value is not used during the SFd phase soft start and during hot gas defrost where the fixed percentace of the valve opening is set by oPd Fot nU Manual open...

Page 11: ... closer of the valve and then will restart working REGULATION SET 5 0 Set point LS US Target set point for temperature regulation HY 2 Differential 0 1 C to 25 5 C 1 F to 45 F If CrE n then HY is the hysteresis for ON OFF thermoregulation If CrE Y or CrE EUP then HY is the proportional band for temperature PI controller On these cases the value should be greater than 5 C int 150 Integral time for ...

Page 12: ...evaporator probe is present idF 6 Defrost interval 0 to 120hours It sets the time interval between the beginning of two defrost cycles EdF in it is the interval between 2 defrost EdF rtC it is the safety interval in case of clock alarm RtC RtF idF 0 the defrost can be activated only manually or through RS485 or from external contact or from LAN MdF 45 Maximum duration for defrost 0 to 255min When ...

Page 13: ... reached and the ALd delay time is expired the LA alarm will be enabled AHY 1 0 Differential for room temperature alarm 0 1 C to 25 5 C 1 F to 45 F Threshold recovery after a temperature alarm ALd 15 Room Temperature alarm delay 0 to 255min Time interval between the detection of an alarm condition and the corresponding alarm signaling dLU 150 High temperature alarm detected by defrost probe dLL 15...

Page 14: ...P CL Digital input 3 polarity OP CL CL means the digital input is activated by closing the contact OP means the digital input is activated by opening the contact i3F ES Digital input 3 configuration EAL bAL PAL dor dEF AUS LiG OnF Htr FHU ES HdY EAL external alarm bAL serious external alarm PAL pressure switch activation dor door open dEF defrost activation AUS auxiliary activation LiG light activ...

Page 15: ...C ntC P1 configuration nP PtC ntC CtC PtM nP not present PtC Ptc ntC ntc CtC ntc US PtM Pt1000 Ot 0 P1 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the thermostat probe P2C ntC P2 configuration nP PtC ntC CtC PtM nP not present PtC Ptc ntC ntc CtC ntc US PtM Pt1000 oE 0 P2 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the evaporator probe P3C nP P3 configurat...

Reviews: