1592023140 XM678D GB r2.8 01.09.2017.docx
XM678D
15/
15
LABEL
VALUE
DESCRIPTION
RANGE
NOTES
LOF
n
LAN ON/OFF Synchronization.
n; Y
This parameter states if the On/Off command of the section will act
on all the other ones too:
n
= the On/Off command acts only in the local section;
Y
= the On/Off command is sent to all the other sections.
LLi
y
LAN Light Synchronization.
n; Y
This parameter states if the light command of the section will act
on all the other ones too:
n
= the light command acts only in the local section;
Y
= the light command is sent to all the other sections.
LAU
n
AUX Synchronization.
n; Y
This parameter states if the AUX command of the section will act
on all the other ones too:
n
= the light command acts only in the local section;
Y
= the light command is sent to all the other sections.
LES
n
Energy Saving Synchronization.
n; Y
This parameter states if the energy saving command of the section
will act on all the other ones too:
n
= the Energy Saving command acts only in the local section;
Y
= the Energy Saving command is sent to all the other sections.
LSd
n
Remote probe displaying.
n; Y
This parameter states if the section has to display the local probe
value or the value coming from another section:
n
= the displayed value is the local probe one;
Y
= the displayed value is the one coming from another section
(which has parameter
LdS = Y
).
LPP
y
Pressure probe through the LAN.
n; Y
n =
the value of pressure probe is read from local probe;
Y =
the value of pressure probe is sent via LAN.
LCP
n
Probe 4 through the LAN.
n; Y
StM
n
Cooling request from LAN enable
compressor relay.
n; Y
n =
not used;
Y =
a generic cooling requests from LAN activate the solenoid valve
connected to compressor relay.
ACE
n
Cooling request from LAN enable even if
compressor is stopped by door switch
n; Y
n =
not used;
Y =
a generic cooling requests from LAN activate the solenoid valve
connected to compressor relay.
PROBE CONFIGURATION
NTC (10KΩ a 25°C), PtC (806Ω a 0°C)
P1C
ntC
P1 configuration.
nP; PtC; ntC; CtC; PtM
nP
=
not present;
PtC
=
Ptc;
ntC
=
ntc;
CtC
=
ntc US
PtM
=
Pt1000.
Ot
0
P1 calibration.
[-12.0°C to 12.0°C]
Allows to adjust possible offset of the thermostat probe.
P2C
ntC
P2 configuration.
nP; PtC; ntC; CtC; PtM
nP
=
not present;
PtC
=
Ptc;
ntC
=
ntc;
CtC
=
ntc US
PtM
=
Pt1000.
oE
0
P2 calibration.
[-12.0°C to 12.0°C]
Allows to adjust possible offset of the evaporator probe.
P3C
nP
P3 configuration.
nP; PtC; ntC; CtC; PtM
nP
=
not present;
PtC
=
Ptc;
ntC
=
ntc;
CtC
=
ntc US
PtM
=
Pt1000.
O3
0
P3 calibration.
[-12.0°C to 12.0°C]
Allows to adjust possible offset of the probe 3.
P4C
nP
P4 configuration.
nP; PtC; ntC; CtC; PtM; LAN
nP
=
not present;
PtC
=
Ptc;
ntC
=
ntc;
CtC
=
ntc US
PtM
=
Pt1000;
LAN
= value received from master.
O4
0
P4 calibration.
[-12.0°C to 12.0°C]
Allows to adjust possible offset of the probe 4.
P5C
420
P5 configuration.
nP; PtC; ntC; CtC;
PtM; 420; 5Vr; LAN
nP
=
not present;
PtC
=
Ptc;
ntC
=
ntc;
CtC
=
ntc US;
PtM
=
Pt1000;
420
=
4 to 20mA;
5Vr
=
0 to 5V ratiometric;
LAN
= value
received from master.
o5
0
P5 calibration.
[-12.0°C to 12.0°C]
Allows to adjust possible offset of the probe 5.
P6C
PtM
P6 configuration.
nP; PtC; ntC; CtC; PtM
nP
=
not present;
PtC
=
Ptc;
ntC
=
ntc;
CtC
=
ntc US
PtM
=
Pt1000.
o6
0
P6 calibration.
[-12.0°C to 12.0°C]
Allows to adjust possible offset of the probe 6.
SERVICE
CLt
- - -
ON/OFF percentage (C.R.O.).
(read only)
It shows the effective cooling time calculated by XM600 during
regulation (cooling time percentage).
tMd
- - -
Time remaining before next defrost
activation (only for interval defrost).
(read only)
It shows time before the next defrost when interval defrost is
selected.
LSn
Auto
Number of devices in LAN.
1 to 8 (read only)
Shows the number of sections available in the LAN.
LAn
Auto
List of address of LAN devices.
1 to 247 (read only)
Identifies the instrument address (
1 to LSn
) inside local network of
multiplexed cabinet controller.
Adr
1
ModBUS address.
1 to 247
Identifies the instrument address when connected to a ModBUS
compatible monitoring system.
rEL
2.8
Firmware release.
(read only)
Microprocessor firmware release.
Ptb
- - -
Parameter table.
(read only)
It shows the original code of the Dixell parameter map.
Pr2
- - -
Pr2 menu access.
(read only)
Access to the protected parameter list
.