1592023140 XM678D GB r2.8 01.09.2017.docx
XM678D
14/
15
LABEL
VALUE
DESCRIPTION
RANGE
NOTES
CoM
Cur
Modulating output configuration.
PM5; PM6; OA7;
CUr; tEn
For models with PWM / O.C. output:
- PM5
=
PWM 50Hz;
- PM6
=
PWM 60Hz;
- OA7
=
two state, it can be used as an open collector output.
For models with [4 to 20mA] or [0 to 10V] output:
- Cur
=
4 to 20mA current output;
- tEn
=
0 to 10V voltage output.
AOP
CL
Alarm relay polarity.
OP; CL
CL
=
normally closed;
OP
=
normally opened.
iAU
n
Auxiliary output independent from
ON/OFF state.
n; Y
n
=
if the instrument is switched off also the auxiliary output is
switched off;
Y
=
the auxiliary output state is unrelated to the ON/OFF device
status.
DIGITAL INPUTS
i1P
CL
Digital input 1 polarity.
OP; CL
CL
= the digital input is activated by closing the contact;
OP
= the digital input is activated by opening the contact.
i1F
dor
Digital input 1 configuration.
EAL; bAL; PAL;
dor; dEF; AUS;
LiG; OnF; Htr;
FHU; ES; HdY
EAL
=
external alarm;
bAL
=
serious external alarm;
PAL
=
pressure switch activation;
dor
=
door open;
dEF
=
defrost activation;
AUS
=
auxiliary activation;
LiG
=
light activation;
OnF
=
switch on/off the instrument;
Htr
=
change type of action;
FHU
=
not used;
ES
=
activate energy saving;
HdY
=
activate holiday function.
d1d
15
Digital input 1 activation delay.
0 to 255min
When
[i1F
=
PAL]
: time interval to calculate the number of the
pressure switch activation.
When
[i1F = EAL
or
bAL]
(external alarms):
d1d
parameter
defines the time delay between the detection and the successive
signaling of the alarm.
When
[i1F = dor]
:
this is the delay to activate door open alarm.
i2P
CL
Digital input 2 polarity.
OP; CL
CL
means the digital input is activated by closing the contact;
OP
means the digital input is activated by opening the contact.
i2F
LiG
Digital input 2 configuration.
EAL; bAL; PAL;
dor; dEF; AUS;
LiG; OnF; Htr;
FHU; ES; HdY
EAL
=
external alarm;
bAL
=
serious external alarm;
PAL
=
pressure switch activation;
dor
=
door open;
dEF
=
defrost activation;
AUS
=
auxiliary activation;
LiG
=
light activation;
OnF
=
switch on/off the instrument;
Htr
=
change type of action;
FHU
=
not used;
ES
=
activate energy saving;
HdY
=
activate holiday function.
d2d
5
Digital input 2 activation delay.
0 to 255min
When
[i2F
=
PAL]
: time interval to calculate the number of the
pressure switch activation.
When
[i2F = EAL
or
bAL]
(external alarms):
d2d
parameter
defines the time delay between the detection and the successive
signaling of the alarm.
When
[i2F = dor]
:
this is the delay to activate door open alarm.
i3P
CL
Digital input 3 polarity.
OP; CL
CL
means the digital input is activated by closing the contact;
OP
means the digital input is activated by opening the contact.
i3F
ES
Digital input 3 configuration.
EAL; bAL; PAL;
dor; dEF; AUS;
LiG; OnF; Htr;
FHU; ES; HdY
EAL
=
external alarm;
bAL
=
serious external alarm;
PAL
=
pressure switch activation;
dor
=
door open;
dEF
=
defrost activation;
AUS
=
auxiliary activation;
LiG
=
light activation;
OnF
=
switch on/off the instrument;
Htr
=
change type of action;
FHU
=
not used;
ES
=
activate energy saving;
HdY
=
activate holiday function.
d3d
0
Digital input 3 activation delay.
0 to 255min
When
[i3F
=
PAL]
: time interval to calculate the number of the
pressure switch activation.
When
[i3F = EAL
or
bAL]
(external alarms):
d3d
parameter
defines the time delay between the detection and the successive
signaling of the alarm.
When
[i3F = dor]
:
this is the delay to activate door open alarm.
nPS
15
Number of pressure switch activations
before lock.
0 to 15
Number of activation of the pressure switch, during the
d1d, d2d
and
d3d
interval, before signaling the alarm event
[i1F, i2F or i3F
= PAL]
. If the
nPS
activation in the
d1d, d2d or d3d
time is
reached, switch off and on the instrument to restart normal
regulation.
OdC
F-C
Compressor and fan status when open
door.
no; FAn; CPr; F-C
no
= normal;
Fan
= Fan OFF;
CPr
= Compressor OFF;
F_C
= both Compressor and Fan OFF.
rrd
15
Output restart delay with door open.
0 to 255min
The outputs stopped by the
OdC
parameter can restart after
rrd
time.
ENERGY SAVING
ESP
P1
Energy saving probe selection.
nP; P1; P2; P3; P4; P6; tEr
-
HES
0.0
Temperature increasing during Energy
Saving.
[-30.0°C to 30.0°C]
[-54°F to 54°F]
Sets the increasing value of the set point during the Energy Saving
cycle.
PEL
nU
Energy saving activation when Light
or/and AUX are switched off.
nU(0); LIG(1); AUS(2); LEA(3)
Energy saving enabled when:
-
LiG
: light switched off;
-
AUS
: AUX switched off;
-
LEA
: both light and AUX switched off.
If
nU
then not used function.
LAN MANAGEMENT
LMd
y
Defrost Synchronization.
n; Y
n
= the section doesn’t send a global defrost command;
Y
= the section sends a command to start defrost to other
controllers.
dEM
y
Defrost end Synchronization.
n; Y
n
= the end of the LAN defrosts are independent;
Y
= the end of the LAN defrosts are synchronized.
LSP
n
LAN set-point Synchronization.
n; Y
n
= the set-point value is modified only in the local section;
Y
= the section set-point, when modified, is updated to the same
value on all the other sections.
LdS
n
LAN Display Synchronization
(temperature sent via LAN).
n; Y
n
= the set-point value is modified only in the local section;
Y
= the value displayed by the section is sent to all the other
sections.