MODBUS Termination Blocks
Default Setting Values • 43
tdF
EL
Pr1
Defrost type
EL(0) - in(0)
EdF
in
Pr1
Defrost mode: Interval
in(1)
Srt
150
Pr1
Heater setpoint during defrost
[-67°F to 302°F]
[-55.0°C to 150°C]
Hyr
2.0
Pr1
Differential for heater
[1°F to 45°F]
[0.1°C to 25.5°C]
tod
255
Pr1
Time out for heater
0 to 255 (min.)
dtP
0.1
Pr1
Minimum temperature difference to start
defrost
[1°F to 90°F]
[0.1°C to 50.0°C]
ddP
60
Pr1
Delay before starting defrost
0 to 60 (min.)
d2P
n
Pr1
Defrost with two probes
n(0) – Y(1)
dtE
8.0
Pr1
Defrost termination temperature
(Probe A)
[-67°F to 122°F]
[-55.0°C to 50.0°C]
dtS
8.0
Pr1
Defrost termination temperature
(Probe B)
[-67°F to 122°F]
[-55.0°C to 50.0°C]
idF
6
Pr1
Interval between defrosts
0 to 120 (hours)
MdF
30
Pr1
Defrost Maximum duration
0 to 255 (min.)
dSd
0
Pr1
Start defrost delay
0 to 255 (min.)
dFd
it
Pr1
Display during defrost
rt(0) - it(1) - SEt(2) - dEF(3)
dAd
30
Pr1
Defrost display time out
0 to 255 (min.)
Fdt
0
Pr1
Drain down time
0 to 255 (min.)
dPo
n
Pr1
Defrost at start-up
n(0) – Y(1)
dAF
0.0
Pr1
Defrost delay after continuous cycle
0 to 24.0(144)(hours.10min)
FAN
FPA
P2
Pr1
Fan probe A
nP(0) - P1(1) - P2(2) - P3(3) - P4(4) -
P5(5)
FPb
nP
Pr1
Fan probe B
nP(0) - P1(1) - P2(2) - P3(3) - P4(4) -
P5(5)
FPE
100
Pr1
Virtual probe percentage
(fan management)
0 to 100 (100=FPA, 0=FPb)
FnC
O-n
Pr1
Fan operating mode
C-n(0) - O-n(1) - C-y(2) - O-y(3)
Fnd
10
Pr1
Fan delay after defrost
0 to 255 (min.)
FCt
10
Pr1
Temperature differential to avoid short
cycles of fans
[0°F to 90°F]
[0.0°C to 50.0°C]
FSt
2.0
Pr1
Fan stop temperature
[-67°F to 122°F]
[-55.0°C to 50.0°C]
FHy
1.0
Pr1
Fan stop differential
[1°F to 45°F]
[0.1°C to 25.5°C]
Fod
0
Pr1
Fan activation time after defrost
(without compressor)
0 to 255 (min.)
Fon
0
Pr1
Fan ON time
0to15 (min.)
FoF
0
Pr1
Fan OFF time
0to15 (min.)
trA
UAL
Pr2
Kind of regulation for modulating output
UAL(0) - rEG(1) - AC(2)
SOA
80
Pr2
Fixed speed for fan
AMi to AMA
SdP
30.0
Pr2
Default Dew Point value
[-67°F to 122°F]
[-55.0°C to 50.0°C]
Table 23-1 - Default Setting Values (Continued)