24 • XM679K I&O Manual
026-1218 Rev 4
14 Alarm Signals
Message
Cause
Outputs
KEYBOARD
nod
No display: the keyboard is trying to
work with another board that is not
working or not present.
Press the UP arrow for three (3) seconds. Enter the SEC
menu, and select LOC entry.
PON
Keyboard enabled
Outputs unchanged
POF
Keyboard locked
Outputs unchanged
rst
Alarm reset
Alarm relay reset
nOP, nP, nA
Probe not present
Compressor output according to parameter Con and COF
noL
They keyboard is not able to
communicate with the XM679K.
Verify the connection. Call the service.
ALARM FROM PROBE INPUT
P1
First probe failure
Compressor output according to parameters Con and COF
P2
Second probe failure
Defrost end is timed
P3
Third probe failure
Outputs unchanged
P4
Fourth probe failure
Outputs unchanged
P5
Fifth probe failure
Outputs unchanged
P6
Sixth probe failure
Outputs unchanged
PPF
PPF is displayed by slaves of pressure
that don’t receive the value of pressure.
The percentage of the valve opening is fixed at PEO value.
CPF
CPF is displayed when the remote
probe 4 is not working,
The percentage of the valve opening is fixed at PEO value.
TEMPERATURE ALARM
HA
Maximum temperature alarm
Outputs unchanged
LA
Minimum temperature alarm
Outputs unchanged
HAd
Defrost high temperature
Outputs unchanged
LAd
Defrost low temperature
Outputs unchanged
FAd
Defrost low temperature
Outputs unchanged
HAF
Fan high temperature
Outputs unchanged
LAF
Fan high temperature
Outputs unchanged
StP
Stop due to regulation pauses
(Sti and Std parameters)
Compressor and valve OFF
DIGITAL INPUT ALARM
PAL
Lock due to pressure switch
All outputs OFF
dA
Door open
Compressor and fans restarts according to rrd and odc
EA
External alarm
Outputs unchanged
CA
Serious external alarm (i1F=bAL)
All outputs OFF
ELECTRONIC VALVE ALARM
LOP
Minimum operating pressure reached
According to dML
MOP
Maximum operating pressure reached
According to dML
Table 14-1 - Alarm Signals