6 / 8 

10.08.2011

 

Standard Temperature Controls 

Temperature controls should be selected such, that the target 
upper and lower setpoints fall well inside the adjustment range 
and not at the end of the specified range. 
 
Type 

Part Adjustment Range Lowest 

Factory 

Max. 

Temp. Sensor 

No. 

Upper 

Setpoint 

°C 

Differential 

Setpoint 

K

Setpoint 

 

°C 

Setting 

 

°C 

Bulb 

Temp. 

°C 

Charge Type 

Thermostats TS1 Top Operated (with capillary type sensor) 

Thermostats without Off-Switch 

TS1-A2P 

4 530 400 

-30 … +15 

1.5 … 16 

-36 

-1 / -6 

+150 

 

2m 

TS1-A3P 

4 356 700 

-10 … +35 

1.5 … 16 

-23 

+3 / -2 

 

Vapour 

capillary 

TS1-A1A 

4 351 500 

-45 … -10 

 

-55 

-18 / -20 

 

 

 

TS1-A2A

4 351 600

-30 … +15 

1.5 … 16 

-36 

-1 / -6 

+150 

 

2m 

TS1-A3A

4 352 500

-10 … +35 

 

-23 

+3 / -2 

 

 

capillary 

TS1-A4F

4 351 800

-30 … +35 

2.8 … 20 

-35 

+5 / 0 

 

 

and 

Defrost- and  Universal  Thermostat

+100 Adsorption  bulb 

TS1-A5F 

4 458 400 

+20 … +60 

3 … 10 

+10 

+35 / +30 

 

 

 

Thermostats with Off-Switch 

TS1-B1A 

4 366 700 

-45 … -10 

 

-55 

-18 / -20 

 

 

2 m 

TS1-B2A 

4 366 800 

-30 … +15 

1.5 … 16 

-36 

-1 / -6 

+150 

Vapour 

capillary 

TS1-B3A 

4 366 900 

-10 … +35 

 

-23 

+3 / -2 

 

 

and 

TS1-B4F 

4 367 000 

-30 … +35 

2.8 … 20 

-35 

+5 / 0 

+100 

Adsorption 

bulb 

Room Thermostats TS1 Top Operated (with coil type sensor) 

Room Thermostats without Off-Switch, including insulation console 

TS1-A1E 

4 362 800 

-45 … -10 

 

-55 

-18 / -20 

 

 

0 m 

TS1-A2E 

4 355 200 

-30 … +15 

1.5 … 16 

-36 

+4 / +2 

+70 

Vapour 

coil 

TS1-A3E 

4 355 300 

-10 … +35 

 

-23 

+20 / +18 

 

 

 

Room Thermostats with Off-Switch, including insulation console 

TS1-B2E 

4 344 400 

-30 … +15 

1.5 … 16 

-36 

+4 / +2 

+70 

Vapour 

0 m 

TS1-B3E 

4 344 500 

-10 … +35 

 

-23 

+20 / +18 

 

 

coil 

Frost Monitors TS1 Top Operated (with capillary type sensor) 

Frost Monitors without Off-Switch 

TS1-C0P 

4 352 100 

+4.5 … +20 

2.5 fix 

+2 

4.5 / +2 

 

 

6 m 

TS1-D0P 

4 352 200 

+4.5 … +20 

man. reset 

+2 

+2 

+150 

Vapour 

capillary 

Low temp.  cut out 

 

ca. 2.5 fix 

 

 

 

 

 

Summary of Contents for TS1 Series

Page 1: ... delivered in three main housing variants top operated front operated and flush mounted Top operated controls have adjustment spindles at the top and a display scale indicating temperature setpoint and differential at the front A knob which may be permanently plugged onto one of the adjustment spindles comes with every control Frost monitors and room thermostats are derivatives of top operated the...

Page 2: ...spond faster to temperature changes than adsorption and liquid charges Adsorption charge sensor type F Adsorption charged sensor types operate on the basis of a temperature dependent adsorption material which is located inside the bulb only Therefore these sensor types always respond to temperature changes at the bulb only This makes them suitable to applications where it is not always defined whi...

Page 3: ... again Manual reset low pressure contact function Manual reset high temperature On increasing temperature above the upper setpoint contacts 1 2 open contacts 1 4 close and latch Only on falling temperature below lower setpoint and after pressing the manual reset button contacts 1 4 will open and contacts 1 2 will close again Manual reset high temperature contact function For operational safety all...

Page 4: ...30 V DC 3A 24 V DC 6A 12 V DC Vibration resistance 4 g 10 1000 Hz Motor rating UL FLA 24A 120 240V AC Approvals Locked rotor UL LRA 144A 120 240V AC Low Voltage Directive all models Bellows heater sensor types A E P 73 23 EWG 93 68 EWG EN 60947 1 60947 5 1 60730 2 9 CE Label not for frost monitors function C or D option 82 k 230V AC DC 12V 24V rating Germanic Lloyd standard models Materials when u...

Page 5: ...l dimensions and drawings TS1 Axx Bxx Cxx Dxx TS1 Exx Fxx TS1 Gxx Hxx Sensor type A Vapour charge 2 m capillary with bulb Sensor type P Vapour charge 2 m capillary 6m with function C or D Sensor type E Vapour charge coil 0 m Sensor type F Adsorption charge 2 m capillary with bulb 54 70 Ø 9 2 2 5 Ø 9 5 70 Ø 22 ...

Page 6: ... 351 800 30 35 2 8 20 35 5 0 and Defrost and Universal Thermostat 100 Adsorption bulb TS1 A5F 4 458 400 20 60 3 10 10 35 30 Thermostats with Off Switch TS1 B1A 4 366 700 45 10 55 18 20 2 m TS1 B2A 4 366 800 30 15 1 5 16 36 1 6 150 Vapour capillary TS1 B3A 4 366 900 10 35 23 3 2 and TS1 B4F 4 367 000 30 35 2 8 20 35 5 0 100 Adsorption bulb Room Thermostats TS1 Top Operated with coil type sensor Roo...

Page 7: ...pe sensor Room Thermostats without Off Switch including insulation console TS1 E1E 4 365 300 45 10 2 16 55 18 20 0 m TS1 E2E 4 356 800 30 10 1 5 15 36 4 2 70 Vapour coil TS1 E3E 4 356 900 10 25 1 5 15 23 20 18 Room Thermostats with Off Switch including insulation console TS1 F1E 4 368 000 45 10 2 16 55 18 20 TS1 F2E 4 368 100 30 10 1 5 15 36 4 2 70 Vapour 0 m TS1 F3E 4 368 200 10 25 1 5 15 23 20 1...

Page 8: ...ations failures may occur The suitability for this has to be assured from the plant manufacturer which may include making appropriate tests Since conditions of use are outside of ALCO S control we can not assume any liability for results obtained or damages occurred due to improper application This document replaces all earlier versions Emerson Electric GmbH Co OHG ALCO CONTROLS Postfach 1251 Heer...

Reviews: