background image

2

Pressure Regulators with Type SP/P Safety Pilot

Specifications

This section lists the specifications for the Spence™ regulators with Type SP/P Pressure Safety Pilot. Factory 

specifications are stamped on the nameplate fastened on the regulator at the factory.

Type E Main Valve

Available Sizes

NPS 3/8, 1/2, 34, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3, 4, 5, 

6, 8, 10 and 12 / DN 10, 15, 20, 25, 32, 40, 50, 65, 

80, 100, 125, 150, 200, 250 and 300

End Connection Styles

NPT, CL125, CL150, CL250, CL300 and CL600

Pressure Rating

(1)

See Table 1

Temperature Rating

(1)

 

See Table 1

Rated Flow Coefficient

See Table 2

Construction Materials

Cast Iron and Cast Steel

Type D Pilot

Maximum Inlet Temperature

(1)

Cast Iron:

 450°F / 232°C

Steel:

 750°F / 400°C

Maximum Inlet Pressure

(1)

Cast Iron:

 250 psig / 17.2 bar

Steel:

 600 psig / 41.4 bar

Pressure Ranges

(1)

Type D:

 3 to 150 psig / 0.21 to 10.3 bar

Type D2:

 100 to 300 psig / 6.90 to 20.7 bar

Type D5:

 1 to 25 psig / 0.07 to 1.72 bar

Type D120:

 5 to 300 psig / 0.35 to 20.7 bar

Construction Materials

Cast Iron and cast Steel

Type SP/P Safety Pilot

Maximum Inlet Temperature

(1)

Bronze:

 500°F / 260°C

Steel:

 750°F / 400°C

Maximum Inlet Pressure

(1)

Bronze:

 300 psig / 20.7 bar

Steel:

 600 psig / 41.4 bar

Pressure Ranges

(1)

5 to 13 psig / 0.35 to 0.90 bar

13 to 30 psig / 0.90 to 2.07 bar

31 to 65 psig / 2.14 to 4.48 bar

66 to 120 psig / 4.55 to 8.27 bar

121 to 175 psig / 8.35 to 12.1 bar

Construction Materials

Bronze and Cast steel

1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.

Table 1.

 Type E Main Valve Pressure and Temperature Rating

(1)

MAIN VALVE 

MATERIAL

END CONNECTION

PRESSURE RATING

TEMPERATURE RATING

psig

bar

°F

°C

Cast Iron

250 NPT

250

17.2

406

207

CL125

125

8.62

450

232

CL250

250

17.2

450

232

Cast Steel

300 NPT

300

20.7

600

315

CL150

150

10.3

500

260

CL300

300

20.7

600

315

CL600

600

41.4

600

315

1. Ratings based on maximum inlet conditions.

Table 2

. Type E Main Valve Rated Flow Coefficients

SEAT 

FACTOR

VALVE SIZE, NPS / DN

3/8 / 10 1/2 / 15 3/4 / 20

1 / 25 1-1/4 / 32 1-1/2 / 40 2 / 50 2-1/2 / 65 3 / 80

4 / 100 5 / 125 6 / 150 8 / 200 10 / 250 12 / 300

Full

1.5

2.8

5.4

8.8

14.1

19.8

31

44

74

109

169

248

444

706

1113

Full 75%

- - - -

2.1

4.0

6.6

10.6

14.8

23.3

33

56

82

127

186

333

530

835

Full 50%

- - - -

1.4

2.7

4.4

7.0

9.9

15.5

22

37

55

85

124

222

353

557

Normal

0.65

1.5

4.8

7.5

10.4

14.6

17.6

24

43

78

115

151

249

377

631

Normal 

75%

- - - -

- - - -

- - - -

- - - -

- - - -

- - - -

- - - -

18

33

59

87

114

187

283

474

Normal 

50%

- - - -

- - - -

- - - -

- - - -

- - - -

- - - -

- - - -

12

22

39

58

76

125

189

316

Summary of Contents for SP

Page 1: ...ment could result property damage and personal injury or death Regulator with Type SP P Pressure Safety Pilot must be installed operated and maintained in accordance with federal state and local codes rules and regulations and Emerson Process Management Regulator Technologies Inc Emerson instructions If the regulator vents gas or a leak develops in the system service to the unit may be required Fa...

Page 2: ... Pressure 1 Bronze 300 psig 20 7 bar Steel 600 psig 41 4 bar Pressure Ranges 1 5 to 13 psig 0 35 to 0 90 bar 13 to 30 psig 0 90 to 2 07 bar 31 to 65 psig 2 14 to 4 48 bar 66 to 120 psig 4 55 to 8 27 bar 121 to 175 psig 8 35 to 12 1 bar Construction Materials Bronze and Cast steel 1 The pressure temperature limits in this Instruction Manual and any applicable standard or code limitation should not ...

Page 3: ...st entrance of rain snow insects or any other foreign material that may plug the spring case vent or vent line Type E Main Valve The Type E Main Valve is pilot operated normally closed single seat design featuring packless construction balanced metal diaphragms and protected main spring One or more pilot regulators are mounted to Type E main valve to fit with the specifications defined by the pres...

Page 4: ...t cowl assembly key 20 so that pressure plate key 2 is flush with gage 4 Lock setting by turning barrel locknut key 9 down on bonnet key 11 Tighten barrel lock set screw key 21 Maintenance WARNING To avoid personal injury property damage or equipment damage caused by sudden release of pressure or explosion of accumulated gas do not attempt any maintenance or disassembly without first isolating the...

Page 5: ...re pinched by the valve 7 Tighten hood working back and forth on opposite bolts Do not start on one bolt and work around the circle or you will probably have a leak Safety Pilot 1 Remove the blind flange and using a 15 16 in 23 8 mm long socket remove the seat and disk assembly 2 Remove the stem nuts then clean all parts 3 Lap disk to seat and stem shoulder with fine grinding compound and reassemb...

Page 6: ... Regulator Fails to Close Delivery Pressure Builds Up Too High 1 If there is a bypass valve make sure that it is not leaking 2 Try lowering the delivery pressure by changing the pilot setting 3 Close the stop valves and remove both tubing bends and inspect both the bleedport and restriction ell to make sure they are not obstructed Remove all compression from the pilot adjusting spring and then cra...

Page 7: ... 9 Barrel Locknut Steel WAL4 02910 0 10 B ellows Assembly Broze WAL4 00010 0 Stainless Steel WAL4 00011 0 11 B onnet Bronze WAL4 00979 0 Steel WAL4 00980 0 12 Blind Flange and Bonnet Bolts Steel WAL5 04803 0 13 B ody Bronze WAL4 00856 0 Steel WAL4 00857 0 14 B lind Flange Bronze WAL4 02153 0 Steel WAL4 02152 0 15 Diaphragm 1 2 Stainless steel WAL4 01626 0 16 Hood Iron WAL4 02563 0 17 Cowl Iron WAL...

Page 8: ...merson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are property of their prospective owners The contents of this publication are presented for informational purposes only and while every effort has been made to ensure their accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or services ...