Analog Sensor Control
Software Overview
•
5
-
3
5.2
Analog Sensor Control
The Analog Sensor Control reads the values from one
or more analog sensors, compares them to a set of Cut In/
Cut Out setpoints, and operates a digital output (such as a
relay) based on the analog input in relation to the
setpoints.
An Analog Sensor Control module performs three
functions:
•
COMBINER
- Up to four analog inputs are
combined into a single analog value.
•
CUT IN/CUT OUT CONTROL
- The combined
input value is compared to a Cut In/Cut Out
setpoint. Based on this comparison, a digital output
will be turned ON or OFF.
•
ALARMING
- Alarms and notices can be
generated based on the combined value of the
inputs and its relation to a set of high and low alarm
and notice setpoints.
5.2.1
Control Strategy
The application combines multiple analog inputs into a
single output, using either the primary combination
method or the alternate combination mode, depending on
the state of the Use Alternate Combination property.
The primary and alternate combination methods may
be configured to be one of the following:
• Average - of all defined inputs
Figure 5-1 - Diagram of a Suction Group
SUCTION
PRESSURE
CO
N
D
E
N
S
E
R
DISCHARGE
PRESSURE
LIQUID RECEIVER
CASE CIRC
UIT
OIL
PRESSURE
CIRCUIT
CASE TEMP
(FOR FLOATING)
LIQUID LINE
SOLENOID
26507005
D
D
D
OIL RESET SWITCHES
Input
Sensor Type
Wiring
Instructions
Suction
Pressure
100 lb. Eclipse
transducer
Discharge
Pressure
500 lb. Eclipse
transducer
Oil Pressure
200 lb. Eclipse
transducer
Case Circuit
Temperature
Temperature
Oil Reset
Switches
Digital
Table 5-1 - Suction Group Inputs
Output Device
Wire Output
Board
Contacts to:
Set Failsafe
Dip Switch
to:
Notes
Compressor
N.C. N.C.
(up)
If you want a compressor to be OFF during network/power
loss, use N.O. fail-safes instead.
Unloader
N.C.
N.O. (down)
These fail-safe settings are specifically for unloaders.
Liquid Line
Solenoid (LLS)
N.C.
N.C. (up)
Keeps solenoid energized during network/power loss.
Electric Defrost
N.O.
N.O. (down)
Keeps contacts de-energized during network/power loss.
Table 5-2 - Suction Group Outputs
Summary of Contents for Site Supervisor
Page 1: ...026 1800 Rev 3 02 AUG 2016 Site Supervisor Controller User Guide 2 0 ...
Page 2: ......
Page 13: ...Wiring Diagrams Hardware Overview 1 3 Figure 1 3 Site Supervisor 2 0 Detail ...
Page 29: ...Wiring Examples 3 1 3 Wiring Examples Figure 3 1 Site Supervisor and MultiFlex Wiring ...
Page 31: ...Wiring Examples 3 3 Figure 3 3 Site Supervisor and XR35CX 230V Wiring ...
Page 33: ...Wiring Examples 3 5 Figure 3 5 Site Supervisor and XR75CX Wiring ...
Page 35: ...Wiring Examples 3 7 Figure 3 7 Site Supervisor and XM678 Wiring ...
Page 37: ...Wiring Examples 3 9 Figure 3 9 Site Supervisor and XEV22 Wiring ...
Page 39: ...Wiring Examples 3 11 Figure 3 11 Site Supervisor and XEV32 Wiring ...
Page 41: ...Wiring Examples 3 13 Figure 3 13 Site Supervisor and Thermostat Wiring ...
Page 43: ...Wiring Examples 3 15 Figure 3 14 Site Supervisor and iPro S Wiring ...
Page 121: ......
Page 129: ......
Page 135: ......
Page 139: ......
Page 140: ......