B-4
Site Supervisor Controller User Guide 2.0
No Heat Will Come On
Incorrect board and points
assignment. Check the Heat
OAT lockout temps.
Make sure that your board and points are
assigned to the correct compressors and heat
stages.
1. Log into Site Supervisor.
2. Click the Site Map icon.
3. Under
Control Status
, click
HVAC
.
4. Click
Details
.
5. If
Heat Lockout En
is enabled (set to
ON
), check that
Heat OAT LOCK
is
set to a valid setpoint (temperature)
for heat lock out.
No Cool Will Come On
Incorrect board and points
assignment. Check the Cool
OAT lockout temps.
Make sure that your board and points are
assigned to the correct compressors and heat
stages.
1. Log into Site Supervisor.
2. Click the Site Map icon.
3. Under
Control Status
, click
HVAC
.
4. Click
Details
.
5. If
Cool Lockout En
is enabled (set to
ON
), check that
Cool OAT LOCK
is
set to a valid setpoint (temperature)
for cool lock out.
SYMPTOM
POSSIBLE PROBLEM
SOLUTION
Summary of Contents for Site Supervisor
Page 1: ...026 1800 Rev 3 02 AUG 2016 Site Supervisor Controller User Guide 2 0 ...
Page 2: ......
Page 13: ...Wiring Diagrams Hardware Overview 1 3 Figure 1 3 Site Supervisor 2 0 Detail ...
Page 29: ...Wiring Examples 3 1 3 Wiring Examples Figure 3 1 Site Supervisor and MultiFlex Wiring ...
Page 31: ...Wiring Examples 3 3 Figure 3 3 Site Supervisor and XR35CX 230V Wiring ...
Page 33: ...Wiring Examples 3 5 Figure 3 5 Site Supervisor and XR75CX Wiring ...
Page 35: ...Wiring Examples 3 7 Figure 3 7 Site Supervisor and XM678 Wiring ...
Page 37: ...Wiring Examples 3 9 Figure 3 9 Site Supervisor and XEV22 Wiring ...
Page 39: ...Wiring Examples 3 11 Figure 3 11 Site Supervisor and XEV32 Wiring ...
Page 41: ...Wiring Examples 3 13 Figure 3 13 Site Supervisor and Thermostat Wiring ...
Page 43: ...Wiring Examples 3 15 Figure 3 14 Site Supervisor and iPro S Wiring ...
Page 121: ......
Page 129: ......
Page 135: ......
Page 139: ......
Page 140: ......