User Instructions
Part Number IOM – 87376-7 July 2016, Rev 1.
19
Table 3.
Torque Thread Table (2)
Thread
Tightening Torque [Nm] for Bolts with Strength Grade
8.8
A2-70/A4-70
M6
11
8
M8
25
18
M10
51
36
M12
87
61
M16
214
150
M20
431
294
M30
1489
564
For output type A (unbored threaded bushing), you must sufficiently lubricate both needle
bearings in the output form after processing and cleaning the spindle nut. For this purpose, use
the optional RTS FQ Fail-Safe Quarter-Turn Series grease lubricant or a grease lubricant according
to our
recommendation (see
Section 26.2
, page 84).
12.2
Mounting Position of the Operating Unit
Figure 15
RTS FQ Fail-Safe Quarter-Turn Control System
•
Disconnect the actuator and control system from the power supply.
•
To prevent damage to the electronic components, both the control system and the
person have to be grounded.
•
Undo the bolts for the interface surface and carefully remove the service cover.
•
Turn service cover to new position and put back on.
—
Ensure correct position of the O-ring.
—
Turn service cover by maximum of 180
o
.
—
Put service cover on carefully so that no cables get wedged in.
•
The bolts evenly in a crosswise sequence.
NOTE:
Maximum torque of 5 Nm.
Summary of Contents for RTS FQ
Page 2: ...User Instructions Part Number IOM 87376 7 July 2016 Rev 1 0 ii ...
Page 6: ...User Instructions Part Number IOM 87376 7 July 2016 Rev 1 0 iv ...
Page 7: ...User Instructions Part Number IOM 87376 7 July 2016 Rev 1 v ...
Page 89: ...User Instructions Part Number IOM 87376 7 July 2016 Rev 1 0 82 ...