3.4.8
Traditional architecture cable
200 ft (61 m) maximum length
3.4.9
Power consumption of transmitter probe/integral
autocal probe
776 W maximum during warm-up
3.5
Installation specifications - Rosemount 6888 Xi
with Rosemount 6888C Transmitter probe
3.5.1
Electrical power of optional Rosemount 6888 Xi
Electronics
120/240 V ±10%, 50/60 Hz
3.5.2
Power consumption of Rosemount 6888 Xi
10 W maximum
3.5.3
Rosemount 6888 Xi alarm relays
2 provided- 2 amps, 20 Vdc
3.5.4
Rosemount 6888 Xi optional loss of flame contact
Removes heater power
3.5.5
Electrical noise
Meets EN 61326, Class A
3.5.6
Traditional architecture cable
200 ft (61 m) maximum length
3.5.7
Transmitter electrical 4-20 mA power
12 - 42 Vdc (looped-powered from the control room or from the Rosemount 6888 Xi box)
Specifications
Instruction Manual
July 2018
00809-0100-4891
18
6888C
Summary of Contents for Rosemount 6888C
Page 10: ...General information Instruction Manual July 2018 00809 0100 4891 10 6888C ...
Page 14: ...Typical system package Instruction Manual July 2018 00809 0100 4891 14 6888C ...
Page 20: ...Specifications Instruction Manual July 2018 00809 0100 4891 20 6888C ...
Page 46: ...Install Instruction Manual July 2018 00809 0100 4891 46 6888C ...
Page 55: ...Instruction Manual Calibration 00809 0100 4891 July 2018 Instruction Manual 55 ...
Page 56: ...Calibration Instruction Manual July 2018 00809 0100 4891 56 6888C ...
Page 61: ...Instruction Manual HART menu trees 00809 0100 4891 July 2018 Instruction Manual 61 ...
Page 62: ...HART menu trees Instruction Manual July 2018 00809 0100 4891 62 6888C ...
Page 78: ...Maintenance and service Instruction Manual July 2018 00809 0100 4891 78 6888C ...
Page 82: ...Service support Instruction Manual July 2018 00809 0100 4891 82 6888C ...
Page 87: ...Instruction Manual 00809 0100 4891 July 2018 Instruction Manual 87 ...