78
Reference Manual
00809-0200-4728, Rev SA
Troubleshooting
July 2018
Troubleshooting
6.4.2
Warning status
Sensor short
ALARM
SNSR 1
ALARM
FAIL
ALARM
SNSR 1
ALARM
FAIL
This message indicates that
the transmitter has detected a
shorted sensor condition. The
sensor may be disconnected,
connected improperly, or
malfunctioning.
1. Verify the process temperature is within the
specified sensor's range. Use the Sensor
Information button to compare with the
process temperature.
2. Verify the sensor is properly wired and
connected to the terminals.
3. Verify the integrity of the sensor and sensor
lead wires. If the sensor is faulty, repair or
replace the sensor.
Terminal
temperature
failure
ALARM
TERM
ALARM
FAIL
ALARM
TERM
ALARM
FAIL
The terminal temperature is
outside the internal RTD’s
specified operating range.
1. Verify the ambient temperature is within the
device specified operating range using the
terminal temperature information button.
Invalid
configuration
CONFG
SNSR 1
WARN
ERROR
CONFG
SNSR 1
WARN
ERROR
The sensor configuration
(type and/or connection)
does not match the sensor
output and is invalid.
1. Verify sensor type and number of wires
matched the sensor configuration of the
device.
2. Reset the device.
3. If error persists, download the transmitter
configuration.
4. If error still present, replace the transmitter.
Field device
malfunction
ALARM
DEVICE
ALARM
FAIL
ALARM
DEVICE
ALARM
FAIL
The device has malfunctioned
or needs immediate
attention.
1. Perform a processor reset.
2. View other alerts to see if the transmitter
indicates a specific problem.
3. If the condition persists, replace the device.
1.
Sensor 1 is used here as an example. If Dual Sensors are ordered this alert can apply to either sensor.
Alert name
LCD screen
LOI screen
Problem
Recommended action
Hot Backup
™
Active
HOT BU
SNSR 1
HOT BU
FAIL
HOT BU
SNSR 1
HOT BU
FAIL
Sensor 1 has failed (open or
shorted) and Sensor 2 is now
the primary process variable
output.
1. Replace Sensor 1 at you earliest
convenience.
2. Reset Hot Backup feature in the device
software.
Sensor drift alert
active
(1)
WARN
DRIFT
WARN
ALERT
WARN
DRIFT
WARN
ALERT
The difference between
Sensor 1 and 2 has gone
beyond the user-configured
Drift Alert Threshold.
1. Verify sensor connections are valid on the
transmitter.
2. If necessary, check calibration of each
sensor.
3. Verify process conditions match sensor
outputs.
4. If calibration fails, one of the sensors has
failed. Replace it at your earliest
convenience.
Table 6-2. Failed – Fix Now
Alert name
LCD screen
LOI screen
Problem
Recommended action
Summary of Contents for Rosemount 644 with HART Protocol
Page 2: ......
Page 8: ...vi Reference Manual 00809 0200 4728 Rev SA Title Page July 2018 Title Page ...
Page 48: ...40 Reference Manual 00809 0200 4728 Rev SA Configuration July 2018 Configuration ...
Page 62: ...54 Reference Manual 00809 0200 4728 Rev SA Installation July 2018 Installation ...
Page 111: ......