48
Reference Manual
00809-0200-4728, Rev SA
Installation
July 2018
Installation
5. To verify the correct installation of Integral Transient Protection (option code T1) on the Rosemount
644 device, confirm the following steps have been completed:
a. Ensure the transient protector unit is firmly connected to the transmitter puck assembly.
b. Ensure the transient protector power leads are adequately secured under the transmitter power
terminal screws.
c. Verify the transient protector’s ground wire is secured to the internal ground screw found within
the universal head.
Note
The transient protector requires the use of an enclosure of at least 3.5-in. (89 mm) in diameter.
6. Pull the sensor wiring leads through the universal head and transmitter. Mount the transmitter in the
universal head by threading the transmitter mounting screws into the universal head mounting
holes.
7. Seal adapter threads with thread sealant.
8. Pull the field wiring leads through the conduit into the universal head. Wire the sensor and power
leads to the transmitter (see
“Wiring and powering the transmitter” on page 55
). Avoid contact with
other terminals.
9. Install and tighten the universal head cover. Enclosure covers must be fully engaged to meet
explosion-proof requirements.
A. Rosemount 644 Transmitter
B. Universal junction box
C. Threaded style sensor
D. Extension
E. Threaded thermowell
A
B
C
D
E
Summary of Contents for Rosemount 644 with HART Protocol
Page 2: ......
Page 8: ...vi Reference Manual 00809 0200 4728 Rev SA Title Page July 2018 Title Page ...
Page 48: ...40 Reference Manual 00809 0200 4728 Rev SA Configuration July 2018 Configuration ...
Page 62: ...54 Reference Manual 00809 0200 4728 Rev SA Installation July 2018 Installation ...
Page 111: ......