L_TYPE is
indirect
When an inferred measurement is made based on the sensor
measurement, set the XD_SCALE to represent the operating range that
the sensor will see in the process. Determine the inferred measurement
values that correspond to the XD_SCALE 0 and 100% points and set these
for the OUT_SCALE.
L_TYPE is
indirect
square root
When an inferred measurement is made based on the transmitter
measurement and the relationship between the inferred measurement
and sensor measurement is square root, set the XD_SCALE to represent
the operating range that the sensor will see in the process. Determine the
inferred measurement values that correspond to the XD_SCALE 0 and
100% points and set these for the OUT_SCALE.
Engineering units
Note
To avoid configuration errors, only select engineering units for XD_SCALE and OUT_SCALE
that are supported by the device.
Related information
4.11.2
Factory supplied AI blocks
The Rosemount 5900C is supplied with six pre-configured AI blocks according to
. The block configuration can be changed if needed.
Table 4-6: Factory Supplied AI Blocks for the Rosemount 5900C
AI Block
Channel
L-Type
Units
1
CHANNEL_LEVEL
Direct
Meter
2
CHANNEL_DISTANCE
Direct
Meter
3
CHANNEL_LEVELRATE
Direct
Meter per hour
4
CHANNEL_SIGNAL_STRENGTH
Direct
mV
5
CHANNEL_HOUSING_TEMPERATURE
Direct
deg C
6
CHANNEL_VOLUME
Direct
m
3
4.11.3
Modes
The AI Function Block supports three modes of operation as defined by the MODE_BLK
parameter:
Manual (Man)
The block output (OUT) may be set manually.
Automatic
(Auto)
OUT reflects the analog input measurement or the simulated value
when simulation is enabled.
Out of Service
(O/S)
The block is not processed. FIELD_VAL and PV are not updated and
the OUT status is set to Bad: Out of Service. The BLOCK_ERR
parameter shows Out of Service. In this mode, you can make
Reference Manual
Configuration
00809-0100-5901
September 2019
Rosemount 5900C Radar Level Gauge
163
Summary of Contents for Rosemount 5900C
Page 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Page 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Page 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Page 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Page 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...