Quick Start Guide

00825-0200-4088, Rev CB

September 2018

Rosemount

 4088B MultiVariable

Transmitter

with Bristol

 Standard Asynchronous/

Synchronous Protocol (BSAP)/MVS

Protocol

Summary of Contents for Rosemount 4088B MultiVariable

Page 1: ...Quick Start Guide 00825 0200 4088 Rev CB September 2018 Rosemount 4088B MultiVariable Transmitter with Bristol Standard Asynchronous Synchronous Protocol BSAP MVS Protocol ...

Page 2: ...struments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices In an Explosion proof Flameproof installation do not remove the transmitter covers when power is applied to the unit Process leaks may cause harm or result in death Install and tighten process connectors before applying pressure Electrical shock can result in death or serious injury Av...

Page 3: ...September 2018 Quick Start Guide Quick Start Guide 3 ...

Page 4: ...ter Consider housing rotation Consider Housing Rotation Set the switches Set the Switches Wiring and power up Wiring and Power Up Verify device configuration Verify Device Configuration Trim the transmitter Trim the Transmitter Finish September 2018 Quick Start Guide Quick Start Guide 5 ...

Page 5: ...taps 3 Mount the transmitter so that the drain vent valves are oriented upward A A Direction of flow 2 2 Gas flow applications Procedure 1 Place taps in the top or side of the line 2 Mount beside or above the taps A A Direction of flow Quick Start Guide September 2018 6 Rosemount 4088B MultiVariable Transmitter Quick Start Guide ...

Page 6: ...to the side of the line 2 Mount beside or below the taps 3 Fill impulse lines with water A A Direction of flow 2 4 Mounting brackets Figure 2 1 Mounting Bracket Coplanar Flange Panel mount Pipe mount September 2018 Quick Start Guide Quick Start Guide 7 ...

Page 7: ...flange manifold or flange adapters follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitter Only use bolts supplied with the transmitter or sold by Emerson as spare parts Figure 2 4 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly Quick Start Guide September 2018 8 Rosemount 4088B Multi...

Page 8: ...al by viewing the markings on the head of the bolt and referencing Table 2 1 If bolt material is not shown in Table 2 1 contact the local Emerson representative for more information Use the following bolt installation procedure Procedure 1 Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation However no additional lubricant sho...

Page 9: ...e and Flange Adapter Bolts Bolt material Head markings Initial torque Final torque Carbon Steel CS B7M 300 in lb 650 in lb Stainless Steel SST 316 316 316 SW 316 STM 316 R B8M 150 in lb 300 in lb Figure 2 5 Proper Bolt Installation A B A Bolt B Sensor module Quick Start Guide September 2018 10 Rosemount 4088B MultiVariable Transmitter Quick Start Guide ...

Page 10: ...e O rings 2 7 Environmental seal for housing Thread sealing PTFE tape or paste on male threads of conduit is required to provide a water dust tight conduit seal and meets requirements of NEMA Type 4X IP66 and IP68 Consult factory if other Ingress Protection ratings are required For M20 threads install conduit plugs to full thread engagement or until mechanical resistance is met 2 8 In line gage tr...

Page 11: ...Figure 2 6 In line Gage Transmitter A A Low side pressure port under neck label Quick Start Guide September 2018 12 Rosemount 4088B MultiVariable Transmitter Quick Start Guide ...

Page 12: ...efer to the Troubleshooting chapter in the appropriate reference manual for more information Over rotation may sever the electrical connection between the sensor module and the electronics 3 1 Rotate the LCD display About this task Transmitters ordered with the LCD display will be shipped with the display installed In addition to housing rotation the optional LCD display can be rotated in 90 incre...

Page 13: ...ge the four pin connector into the electronics board and snap LCD display into place 4 Required In order to meet explosion proof requirements reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover After the cover is seated properly replace the flathead screw located on the bottom of the housing cover Figure 3 2 Optional LCD Di...

Page 14: ... screwdriver Note The Security switch will need to be in the off position in order to make any configuration changes 4 Required In order to meet explosion proof requirements reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover After the cover is seated properly replace the flathead screw located on the bottom of the housing ...

Page 15: ...d For tapered threads install the plug wrench tight 3 Connect the positive lead from the power source to the PWR terminal and the negative lead to the PWR terminal for power requirements reference 4 Ensure full contact with terminal block screw and washer When using a direct wiring method wrap wire clockwise to ensure it is in place when tightening the terminal block screw Note The use of a pin or...

Page 16: ... Rosemount 4088 MultiVariable Transmitter Reference Manual for more information 6 Reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover in order to meet explosion proof requirements Note Installation of the transient protection terminal block does not provide transient protection unless the transmitter housing is properly gro...

Page 17: ... remove the Rosemount 4088 from the RS 485 network when configuring over the local HART port The device should be taken out of service or put in manual prior to performing any configuration changes Note Certain BSAP parameters such as MANUAL LOCK CFG or EXECUTE CALIB are accessible only through BSAP and must be configured using the TechView component of OpenEnterprise Field Tools Quick Start Guide...

Page 18: ...mitter s local address For more information on Rosemount 4088B configuration calibration tasks in TechView see the TechView User s Guide part D301430X012 Configure the Rosemount 4088B either through a connection with a ROC controller or FloBoss flow computer using the ROCLINK 800 component of OpenEnterprise Field Tools or through a connection with a ControlWave controller or flow computer using th...

Page 19: ...VS or TechView for BSAP protocol G ROC FloBoss or ControlWave flow computer or RTU 5 2 Grounding Signal wire grounding Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical equipment If shielded wiring is used ground the shield of the signal wiring at any one point on the signal loop Device must be properly grounded or earthed according to local electric code...

Page 20: ...cordance with national and local electrical codes The most effective transmitter case grounding method is a direct connection to earth ground with minimal impedance 1 Ω Methods for grounding the transmitter case include Internal ground connection The internal ground connection screw is inside the terminal side of the electronics housing The screw is identified by a ground symbol September 2018 Qui...

Page 21: ...tion is identified by a ground symbol An external ground assembly is included with the option codes shown in Table 5 1 or is available as a spare part 03151 9060 0001 Figure 5 6 External Ground Connection A B A External ground lug B External ground assembly 03151 9060 0001 Quick Start Guide September 2018 22 Rosemount 4088B MultiVariable Transmitter Quick Start Guide ...

Page 22: ...ssembly 5 3 Install optional process temperature input Pt 100 RTD Sensor About this task Note To meet ATEX IECEx Flameproof certification only ATEX IECEx Flameproof cables temperature input code C30 C32 C33 or C34 may be used Procedure 1 Mount the Pt 100 RTD Sensor in the appropriate location Note Use shielded 4 or 3 wire cable for the process temperature connection 2 Connect the RTD cable to the ...

Page 23: ... lug in the housing Figure 5 7 Transmitter RTD Wiring Connection 3 wire 4 wire A Red White B B A C C White Red A Ground Lug B Pt 100 RTD sensor C Connection head Note Verify the installed PT sensor type 3 wire or 4 wire matches the device setting Quick Start Guide September 2018 24 Rosemount 4088B MultiVariable Transmitter Quick Start Guide ...

Page 24: ...onfiguration procedures are given in the ROCLINK Configuration Software User Manual for ROC800 Series part D301250X012 the ROCLINK Configuration Software User Manual for FloBoss 107 part D301249X012 and the TechView User s Guide part D301430X012 The Rosemount 4088 MultiVariable Transmitter Reference Manual contains a detailed register map September 2018 Quick Start Guide Quick Start Guide 25 ...

Page 25: ...lled to the correct level If zero offset is less than 5 percent of USL follow the user interface software instructions below to perform a zero trim on a Field Communicator 7 1 1 Performing a zero trim using OpenEnterprise Field Tools See the product specific ROCLINK manual ROCLINK Configuration Software User Manual for ROC800 Series part D301250X012 or the ROCLINK Configuration Software User Manua...

Page 26: ...ead form Only use plugs adapters glands or conduit with a compatible thread form when closing these entries When installing in a hazardous location use only appropriately listed or Ex certified plugs adapters or glands in cable conduit entries 8 1 European Directive Information A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide The most recent revision of t...

Page 27: ... Installation maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected The manufacturer s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime 2 Flameproof joints are not intended for repair 3 Appropriate cable glands and plugs need to be suitable for a temperature of 5 C gre...

Page 28: ...prevent impact or friction 3 The Rosemount 4088 Transmitters fitted with transient protection are not capable of withstanding the 500 V test This must be taken into account during installation Note Transmitters marked with NI CL 1 DIV 2 can be installed in Division 2 locations using general Division 2 wiring methods or Nonincendive Field Wiring NIFW See Drawing 04088 1206 8 5 Canada All CSA hazard...

Page 29: ... take into account the environmental conditions to which the diaphragm will be subjected The manufacturer s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime 2 Flameproof joints are not intended for repair 3 Appropriate cable glands and plugs need to be suitable for a temperature of 5 C greater than the maximum specified tempera...

Page 30: ...ion if located in a Zone 0 area ND ATEX Dust Certificate FM12ATEX0030X Standards EN 60079 0 2012 A11 2013 EN 60079 31 2014 EN 60529 1991 A1 2000 Markings Ex II 2 D Ex tb IIIC T95 C Ta 20 to 85 C Db Special Conditions for Safe Use X 1 Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66 68 2 Unused cable entries must be filled with suitable blanking plu...

Page 31: ... of the equipment The model code and datasheet are to be consulted for details of the diaphragm material Installation maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected The manufacturer s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime 2 Flameproof joints are not i...

Page 32: ...C 60079 11 2012 This must be taken into account during installation 2 The Rosemount 4088 MV enclosure may be made of aluminum alloy and given a protective polyurethane paint finish however care should be taken to protect it from impact or abrasion if located in a Zone 0 area NK IECEx Dust Certificate IECEx FMG 13 0024X Standards IEC 60079 0 2011 IEC 60079 31 2013 Markings Ex tb IIIC T95 C Ta 20 to...

Page 33: ... ABNT NBR IEC60079 1 2016 ABNT NBR IEC60079 26 2016 Markings Ex db IIC T6 T4 Ga Gb T6 50 Ta 65 C T5 T4 50 Ta 80 C Special Conditions for Safe Use X 1 This device contains a thin wall diaphragm Installation maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected The manufacturer s instructions for installation and maintenance shall be follow...

Page 34: ...wer Pi 1 W 1 W 80 94 mW Capacitance Ci 0 0 0 Inductance Li 0 0 0 Special Conditions for Safe Use X 1 If the equipment is fitted with an optional 90V transient suppressor it is not capable of withstanding the 500 V insulation test required by ABNT NBR IRC 60079 11 This must be taken into account when installing the equipment 2 The enclosure may be made of aluminum alloy and given a protective polyu...

Page 35: ...ion of E1 I1 N1 and ND K2 Combination of E2 and I2 K5 Combination of E5 and I5 K6 Combination of E6 and I6 K7 Combination of E7 I7 N7 and NK KA Combination of E1 I1 E6 and I6 KB Combination of E5 I5 E6 and I6 KC Combination of E1 I1 E5 and I5 KD Combination of E1 I1 E5 I5 E6 and I6 KM Combination of EM and IM Quick Start Guide September 2018 36 Rosemount 4088B MultiVariable Transmitter Quick Start...

Page 36: ...8 11 EU Declaration of Conformity September 2018 Quick Start Guide Quick Start Guide 37 ...

Page 37: ...Quick Start Guide September 2018 38 Rosemount 4088B MultiVariable Transmitter Quick Start Guide ...

Page 38: ...September 2018 Quick Start Guide Quick Start Guide 39 ...

Page 39: ...Quick Start Guide September 2018 40 Rosemount 4088B MultiVariable Transmitter Quick Start Guide ...

Page 40: ...September 2018 Quick Start Guide Quick Start Guide 41 ...

Page 41: ... Baar Switzerland 41 0 41 768 6111 41 0 41 768 6300 RFQ RMD RCC Emerson com Asia Pacific Regional Office Emerson Automation Solutions 1 Pandan Crescent Singapore 128461 65 6777 8211 65 6777 0947 Enquiries AP Emerson com Middle East and Africa Regional Office Emerson Automation Solutions Emerson FZE P O Box 17033 Jebel Ali Free Zone South 2 Dubai United Arab Emirates 971 4 8118100 971 4 8865465 RFQ...