Fnr
Type of fault
Corrective measures
91
Supply voltage is outside the operating
voltage range.
Check the supply voltage and ensure the
voltage supply is correct.
92
Operating temperature of the electronics is
outside the recommended range.
1. Check the temperature of the
transmitter housing considering
ambient and process temperature
conditions.
2. Make necessary adjustments to
adhere to the recommended
operating temperature range.
100
Error while setting parameters using IO-
Link.
Modify the parameter setting using IO-Link
again or reset all parameters to factory
default settings.
Troubleshooting
Quick Start Guide
January 2019
00825-0100-4329
22