3
Operation
This section provides information for using the temperature transmitter.
3.1
Setting Parameters
These options are available when setting parameter values using IO-Link.
•
Reading current process values.
•
Reading, changing and saving current parameter settings and transmitting them to
other units of the same type.
•
Read saved diagnostic information (see
Note
To configure the temperature transmitter, connect the temperature transmitter to a PC
using the IO-Link interface. For more information, go to
.
3.1.1
Adjustable parameters
This table describes parameters that can be modified.
Parameter
Description
Uni
Sets the standard unit of measurement: °F or °C .
OU2
Configuration of the analog signal: I = 4-20 mA or Ineg = 20-4 mA
ASP
Analog start point for measured temperature value
AEP
Analog end point for measured temperature value
drW
Drift warning threshold. If the temperature measurement exceeds the
deviation value, the temperature transmitter sends a warning diagnostic
message when drEd is set to OFF.
•
°F/°C: Maximum permitted temperature deviation of both sensor elements
from the average value.
•
OFF: Drift warning deactivated.
drA
Drift alarm threshold. If the temperature measurement exceeds the deviation
value, the temperature transmitter sends an alarm diagnostic message when
drEd is set to ONdr or OFF.
•
°F/°C: Maximum permitted temperature deviation of both sensor elements
from the average value.
•
OFF: Drift alarm deactivated.
Quick Start Guide
Operation
00825-0100-4329
January 2019
Quick Start Guide
17
Summary of Contents for Rosemount 327T
Page 1: ...Quick Start Guide 00825 0100 4329 Rev 01 January 2019 Rosemount 327T Temperature Transmitter ...
Page 2: ...2 ...
Page 4: ...Contents Quick Start Guide January 2019 00825 0100 4329 4 Quick Start Guide ...
Page 12: ...Introduction Quick Start Guide January 2019 00825 0100 4329 12 Quick Start Guide ...
Page 16: ...Installation Quick Start Guide January 2019 00825 0100 4329 16 Quick Start Guide ...
Page 24: ...Product certifications Quick Start Guide January 2019 00825 0100 4329 24 Quick Start Guide ...