Reference Manual
00809-0100-4840, Rev. BA
July 2008
5-5
Rosemount 3100 Series
e) Press the blue button
→
to move to the next digit. The digit flashes to
indicate it can be edited.
f)
Repeat steps (d) and (e) until the last digit is flashing, and edited as
required.
g) Press the blue button
→
to confirm the fixed loop current.
h) To change the fixed current value to a new value, press the blue button
→
to return to the “
LOOP
” menu and re-start at step (b).
i)
Press the green button
↓
to return to displaying the “
tESt
” menu option.
j)
From “
tESt
”, press the red button
↵
to change to the PV display.
Alternatively, from “
tESt
”, press and hold both the blue
→
and the red
↵
buttons together for 2 seconds to get to the Engineering “
Eng
” menu
(see “Engineering Menu For The 3102 and 3105” on page 5-6.
Summary of Contents for Rosemount 3100 Series
Page 2: ......
Page 4: ......
Page 12: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series 1 4 ...
Page 16: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series 2 4 ...
Page 84: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series A 10 ...
Page 97: ...Reference Manual 00809 0100 4840 Rev BA July 2008 B 13 Rosemount 3100 Series Sheet 2 of 3 ...
Page 98: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series B 14 Sheet 3 of 3 ...
Page 104: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series C 6 ...
Page 114: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series E 6 ...
Page 140: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series F 26 ...
Page 141: ......
Page 142: ......
Page 143: ......