Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
17
S
AFETY
I
NSTRUMENTED
S
YSTEMS
Additional Safety Instrumented Systems information is available in the
Rosemount 3051S reference manual (document number
00809-0100-4801). The manual is available electronically on
www.rosemount.com or by contacting an Emerson Process
Management representative.
3051S Safety-Certified Identification
All 3051S transmitters must be identified as safety-certified before
installing into SIS systems.
NOTE
There are two versions of safety-certified 3051S pressure transmitters.
For transmitters with a yellow SIS circuit board installed and output
code B in the model number, please refer to Manual Supplement
00809-0700-4801.
To identify a safety-certified 3051S:
1. Connect a HART host to the transmitter.
2. Check the software to verify that the software revision is 7 or
higher.
Fast Key Sequence - 1, 5
3. Verify that option code QT is included in the transmitter model
code.
Revision #’s
Fld Dev Rev
7
Software Rev
7
Hardware Rev
16
4801_QIG_RevHA.fm Page 17 Tuesday, February 26, 2008 12:17 PM
Summary of Contents for Rosemount 3051S Series
Page 32: ...Quick Installation Guide 00825 0100 4801 Rev HA February 2008 Rosemount 3051S 32 DOC ...
Page 33: ...Quick Installation Guide 00825 0100 4801 Rev HA February 2008 Rosemount 3051S 33 ...
Page 34: ...Quick Installation Guide 00825 0100 4801 Rev HA February 2008 Rosemount 3051S 34 ...
Page 35: ...Quick Installation Guide 00825 0100 4801 Rev HA February 2008 Rosemount 3051S 35 ...
Page 36: ...Quick Installation Guide 00825 0100 4801 Rev HA February 2008 Rosemount 3051S 36 NOTES ...