Table 4-3: Quick-start Menus
(continued)
Display
Description
Menu item
D. 0.5
1
2
4
10
15
25
35
pF
Sensitivity
Required capacitance increase
between uncovered probe (after
calibration) and switch to output
covered probe
.
Change the preset value only if
required by the application. See
Guide to push-button calibration
The
D
menu item is not valid, and is
not shown if Manual calibration
(menu item
G
) is set to
ON
.
(1)
Factory default setting.
(2)
Standard factory setting is 2 pF. Optional standard settings if ordered.
4.4.1
FSH and FSL settings
•
FSH:
—
Use the FSH setting for full-silo detection applications.
—
Power failure or line break is considered by the electronics to be as
full signal (as protection against overfilling).
•
FSL:
—
Use the FSL setting for empty-silo detection applications.
—
Power failure or line break is considered by the electronics to be as
empty signal (as protection against running dry).
Figure 4-2: FSH and FSL settings