Figure 2-6: Option 1L Grounded Housing
A
B
D
C
A. Sensor wires
B. Transmitters
C. DCS host system
D. Shield ground point
Ground the transmitter: Option 2
Use this method for grounded housing.
Procedure
1. Connect signal wiring shield to the sensor wiring shield.
2. Ensure the two shields are tied together and electrically isolated from the
transmitter housing.
3. Ground shield at the power supply end only.
4. Ensure the sensor shield is electrically isolated from the surrounding grounded
fixtures.
Figure 2-7: Option 2 Grounded Housing
D
B
A
C
A. Sensor wires
B. Transmitters
C. DCS host system
D. Shield ground point
Reference Manual
Installation
00809-0100-4148
June 2019
21