7.3.8
Incorrect level at 100% (20 mA)
Symptom
Measured level is correct at 0% (4 mA) but incorrect at 100% (20 mA).
Figure 7-8: Symptom
A
B
C
D
A. Level
B. Time
C. Actual level
D. Reported level
Possible cause
Upper Range Value is not set correctly.
Recommended actions
•
Check that the Upper Range Value matches the 100% (20 mA) level in the tank.
Related information
Reference Manual
Service and troubleshooting
00809-0100-4480
September 2020
Reference Manual
59