![Emerson Rosemount 1153 Series B Reference Manual Download Page 58](http://html.mh-extra.com/html/emerson/rosemount-1153-series-b/rosemount-1153-series-b_reference-manual_104659058.webp)
Reference Manual
00809-0100-4302, Rev BA
January 2008
Rosemount 1153 Series B
6-8
ORDERING INFORMATION
Table 6-1. Transmitter Design Specifications.
Model
Description
1153
Alphaline
Pressure Transmitters for Nuclear Applications
Code
Pressure Measurement
D
Differential Pressure, 2,000 psig (13.8 MPa) Static Pressure Rating
H
Differential Pressure, 3,000 psig (20.68 MPa) Static Pressure Rating
A
Absolute Pressure
G
Gage Pressure
Code
Series
B
Painted Aluminum Housing; qualified per IEEE Std 323-1974 and IEEE Std 344-1975
Code
PRESSURE RANGES at 68 °F
Rosemount 1153DB
(Differential)
Rosemount 1153HB
(Differential)
Rosemount 1153AB
(Absolute)
Rosemount 1153GB
(Gage)
3
0–5 to 0–30 inH
2
O
(0–1.24 to 0–7.46 kPa)
N/A
N/A
0–5 to 0–30 inH
2
O
(0–1.24 to 0–7.46 kPa)
4
0–25 to 0–150 inH
2
O
(0–6.22 to 0–37.3 kPa)
0–25 to 0–150 inH
2
O
(0–6.22 to 0–37.3 kPa)
N/A
0–25 to 0–150 inH
2
O
(0–6.22 to 0–37.3 kPa)
5
0–125 to 0–750 inH
2
O
(0–31.08 to 0–186.4 kPa)
0–125 to 0–750 inH
2
O
(0–31.08 to 0–186.4 kPa)
0–125 to 0–750 inH
2
O
(0–31.08 to 0–186.4 kPa)
0–125 to 0–750 inH
2
O
(0–31.08 to 0–186.4 kPa)
6
0–17 to 0–100 psi
(0–0.12 to 0–0.69 MPa)
0–17 to 0–100 psi
(0–0.12 to 0–0.69 MPa)
0–17 to 0–100 psi
(0–0.12 to 0–0.69 MPa)
0–17 to 0–100 psi
(0–0.12 to 0–0.69 MPa)
7
0–50 to 0–300 psi
(0–0.34 to 0–2.07 MPa)
0–50 to 0–300 psi
(0–0.34 to 0–2.07 MPa)
0–50 to 0–300 psi
(0–0.34 to 0–2.07 MPa)
0–50 to 0–300 psi
(0–0.34 to 0–2.07 MPa)
8
0–170 to 0–1,000 psi
(0–1.17 to 0–6.89 MPa)
N/A
0–170 to 0–1,000 psi
(0–1.17 to 0–6.89 MPa)
0–170 to 0–1,000 psi
(0–1.17 to 0–6.89 MPa)
9
N/A
N/A
N/A
0–500 to 0–3,000 psi
(0–3.45 to 0–20.68 MPa)
Code
Output
P
Standard 4–20 mA
R
(1)
(1) The Rosemount 1153 Series B with Output Code R Electronics is also available with adjustable damping. This option is specified
by adding “N0037” to the end of the complete model number, for example, 1153DB4RA
N0037
.
Improved Radiation Performance, 4–20 mA
Code
Flange Option
A
Welded
3
/
8
in.
Swagelok
Compression Fitting Process Connection and Welded Drain/Vent Valve
B
(2)
(2) Note: Customer assumes responsibility for qualifying interfaces on these options. Contact Rosemount Nuclear Instruments, Inc. for
details.
¼–18 NPT Process Connection and Welded Drain/Vent Valve
C
(2)
¼–18 NPT Process Connection and Drain Hole (Drain/Vent Valve not supplied)
D
One Flange Code Option A and One Remote Seal
E
(2)
One Flange Code Option B and One Remote Seal
F
(2)
One Flange Code Option C and One Remote Seal
G
Two Remote Seals
H
Welded
3
/
8
in.
Swagelok
Compression Fittings on Both Process Connection and Drain/Vent Connection
J
(2)
Welded
3
/
8
in.
Swagelok
Compression Fitting
Process Connection and ¼–18 NPT Drain Hole
L
One Flange Code Option H and One Remote Seal
M
(2)
One Flange Code Option J and One Remote Seal
Typical Model Number: 1153DB 4 RA
Summary of Contents for Rosemount 1153 Series B
Page 6: ...Reference Manual 00809 0100 4302 Rev BA January 2008 Rosemount 1153 Series B iv ...
Page 9: ...Reference Manual 00809 0100 4302 Rev BA January 2008 TOC 3 Rosemount 1153 Series B ...
Page 10: ...Reference Manual 00809 0100 4302 Rev BA January 2008 Rosemount 1153 Series B TOC 4 ...
Page 12: ...Reference Manual 00809 0100 4302 Rev BA January 2008 Rosemount 1153 Series B 1 2 ...
Page 50: ...Reference Manual 00809 0100 4302 Rev BA January 2008 Rosemount 1153 Series B 5 12 ...
Page 62: ...Reference Manual 00809 0100 4302 Rev BA January 2008 Rosemount 1153 Series B Index 2 ...
Page 63: ......