User Manual
Chapter 1
GFK-2847Y
Aug 2020
Overview
7
1.1.2
Environmental Specifications
Note:
Install the QuickPanel
+
in a well-ventilated location that is not exposed to dust, corrosive
gases or liquids, rain, strong ultra-violet light or direct sunlight, and meets the following
specifications.
Item
IC755CxS06RDx
IC755CxW07CDx
IC755CxS10CDx
IC755CxS12CDx
IC755CxS15CDx
Cooling
Natural convection
Ambient
Operating
Temperature
0 to 55°C (32 to 131 °F)
Ambient
Storage
Temperature
-10 to 60°C (14 to 140 °F)
Ambient
Humidity
(Operating and
Storage)
85% RH Non-condensing, wet-bulb temperature: 30°C (86 °F) or less
Environment
Pollution Degree 2, Indoor use only
Vibration
Resistance
5 to 9 Hz single-amplitude 3.5 mm; 9 to 150 Hz constant-accelerated velocity 9.8m/s2;
X, Y, Z directions 10 time (100 minutes) (Compliance 3502, IEC61131-2 JIS B)
Altitude
800~1114 hPa, altitude up to 2000 m (6561.68 ft)
RoHS
Compliant with EU RoHS Directive 2011/65/EU
Enclosure
Rating
UL Type 4X rating; IP65 in panel mount only