8
FieldQ
April 2017
Installation guide
DOC.IG.QC54.1 Rev.: 2
!
Fig. 5.3 Button board functionality
Closed
Reassignment
button
Status / Auto
Initialization
button
Open
Reassignment
button
5.3.1 “Factory default settings”, using the
button board.
To set the control module to its factory default set-
tings, do the following;
1. Power must be connected according chapter 4
and the Status LED is either on or flashing.
2. Disconnect the power.
3. Press both reassignment (OPEN and CLOSE) but-
tons.
4. Reconnect power.
5. Status LED goes on.
6. Release the reassignment (OPEN and CLOSE)
buttons.
7. Observe that the Status LED indicates that the
unit is in its “Init Default” state (Flashing, see
§5.2)
5.3.2 If auto initialization procedure has failed
(Status LED is flashing)
1. Check supply pressure
2. Check Actuator assembly code (see Installation
& Operation Manual FieldQ Valve Actuator,
DOC.IOM.Q.E)
3. Repeat the initialization procedure.
4. When the actuator does not move within 10
seconds, the auto initialization will fail.
5. To solve this either;
- Perform the “default setting” procedure (see
§5.3.1) and repeat the initialization proce-
dure (see §5.2), or
- Set the limit switch points individually by the
bus see Reference manual QC54,
DOC.RM.QC54.E chapter 3.4.
6 Check functioning
To perform a function test, please see chapter 3 of
Reference manual QC54, DOC.RM.QC54.E.
- After checking the functioning mount the control
module cover to the housing (see figure 3.1).
7 Maintenance
The FieldQ control modules are designed to operate
without maintenance.
For any further maintenance to the actuator see
Installation & Operation Manual FieldQ Valve
Actuator, DOC.IOM.Q.E or contact your local FieldQ
representative.
For any further maintenance to the control module
see Maintenance Manual, DOC.MM.QC54.E or
contact your local FieldQ representative.
Installation, adjustment, putting into service, use,
assembly, disassembly, maintenance and repair of the
control module must be done by qualified personnel.
WARNING
• Substitution of components may impair
suitability of the equipment
Table 2
Button board functionality (see fig. 5.3)
Action
Reassignment buttons
Initialize
Press and confirm press the “Status/Auto-Initialization” button.
Set to factory default
Push both reassignment buttons and hold while powering up. Release
buttons when Status LED is solid.
Switch point re-adjustment
A new switch point can be set by pressing and confirm press the corre-
sponding “Open” or “Closed” button (actuator wil not cycle).