Installation guide
DOC.IG.QC54.1 Rev.: 2
10.4 Wiring instructions QC54 Non Incendive / Non Sparking Control Modules
Unclassified or Non
Hazardous Location
Hazardous or
Classified Location
FF
Power
supply
Warning
* Explosion hazard. Do not disconnect
equipment when a flammable or
combustible atmosphere is present.
* Use installation wiring connections
with admitted maximum operating
temperature of at least 20 ºC (68°F)
higher than maximum ambient.
Electrical Input:
Voltage level:
9 to 30 volts
Current
18 mA maximum
Cable range:
Solid wire
2.5mm
2
max
Stranded wire
0.33 - 2.5mm
2
or 22 - 12 AWG
Protection:
Reverse polarity
Unit is not polarity sensitive.
Required external
Protection
Restrict the power supply cur-
rent to <600mA.
* The current restricted power supply meets NEC
Class 2, as described by the National Electrical
Code® (ANSI/NFPA 70 (NEC®))