AGL_Sol_PEC_01_E_Rev01
5
▪
2 digital inputs opto-isolated (24
– 230 VAC/DC)
▪
2 EEV drivers (for bipolar valve)
▪
1 input for backup power supply (will accommodate an XEC single or double valve, sold separately)
2.3
Advanced technical information
2.3.1 PeC C100 controller
Figure 1
2.3.1.1
Description of the connections
Connector
Description
Connector for 24 VAC/DC power supply (black colour)
Green LED to indicate the presence of power supply
Backup power supply for EXV closing in case of power failure.
Voltage supply range (18-30 VDC) for min 10 sec
Current requirements are dependent on number and type of
EXV
Dry contact, potential free
24-240 VAC/DC, opto-isolated, feedback safety
Connector for relay (5 A resistive, 3 A inductive cos
φ 0.5):
- Relay DO1 (5-6) = 230 V~ potential free
- Relay DO2 (7-8) = 230 V~ potential free
- Relay DO3 (9-10) = 230 V~ potential free
- Relay DO4 (11-12) = 230 V~ potential free
Connector for bipolar valve circuit 1
PE connection for EMC compliance