18
PACSystems™ RX3i 64 MB CPU w/Ethernet Quick Start Guide
GFK-2941K
To enable redundancy in a CPE330 project, select the CPE330 target in the
PME Navigator
and use the
Property Inspector
to change the
Enable
Redundancy
target property to
True
.
PROFINET Controller Configuration
PAC Machine Edition 8.60 SIM 13, PME 9.00 SIM 4 or later may be used to
configure an Embedded PROFINET Controller in the CPE330 Hardware
Configuration on LAN 2.
To enable the PROFINET Controller in a CPE330 project, select the CPE330
2
target in the
PME Navigator
and open the Hardware Configuration. On the
Settings
tab, change the
LAN 2 Mode
to
PROFINET
. The
PROFINET Controller
node description now displays that it is using LAN 2 as a submodule under
the CPE330.
Compatibility with CPU320/CRU320/CPU315
The CPE330 also serves as a drop-in replacement for the CPU320, CRU320,
and CPU315 Controllers without the need to upgrade PME. To download
projects intended for the CPU320/CRU320 to a CPE330 with versions of
PME that do not support the CPE330, you must change the CPE330’s
compatibility setting.
2
CPE330 release 8.90 or later is required for the embedded PNC feature.