User Manual
Section 5
GFK-2958L
May 2021
Detailed Description of I/O Modules
335
Name
Bytes
Bit
Description
Default
Channel 8 error
to
Channel 31 error
19 - 42 0 - 7
Reserved
0
Time stamp
43-46
Time stamp [
μ
s] (32-bit)
5.29.6
Measurement Range EP-3468
Measurement
range
Current (I) /
Voltage (U)
Decimal (D) Hexadecimal Range
Conversion
0
–
20 mA
21.67 mA
29957
0x7505
Overloading
D = 27648 x I / 20
I = D x 20 / 27648
20 mA
27648
0x6C00
Nominal range
10 mA
13824
0x3600
0 mA
0
0x0000
4
–
20 mA
21.67 mA
29957
0x7505
Overloading
D = 27648 x (I
–
4) / 16
I=( D x 16 / 27648 )+ 4
20 mA
27648
0x6C00
Nominal range
12 mA
13824
0x3600
4 mA
0
0x0000
3.6 mA
-691
0XFD4D
Underloading
The following applies for all ranges:
input value > overload range = 0x7FFF
input value < underload range = 0x8000