Programming
CM-2201/CM-2202
7.3.11
Reset Module
This
selection
resets
controller
memory
parameters
to
factory
default
values. If
the
controllers
memory
becomes
corrupt, resetting the module will force the controller to
overwrite
each
register and
may
correct
any
problems
that
exist.
1. Display Mode: Advance
2. Range: yes, no
3. Default: no
7.4
Program- System Test
7.4.1
System Test
This message displays the name of the sub-menu when
entered.
1. Display Mode: Advanced
2. Range: N/A
3. Default: N/A
7.4.2
Alarm Output Test
This function is used for testing and commissioning
purposes allowing the alarm output to be forced On either for
a short period of time or continuously. At the end of the
specified
time
duration,
the
testing
option
is
automatically
disabled. The alarm test function will not operate if the
alarm configuration is set to disable and the message
“ALARM DISABLED” will appear.
1. Display Mode: Advanced
2. Range: 1-24 hours, Disabled, Continuously
3. Default: disabled
7.4.3
Heater Test
This
function
overrides
heater
control
for
maintenance
purposes. For normal operation, set to
“disable”.
If
a
period
of
time
is
selected, the
heater
is
forced On
or
Off for the
selected interval. If
“continuous”
is
selected the heater is
forced
On
or
Off until “disable
"
is
selected.
1. Display Mode: Advanced
2. Range: 1-24 hours, Disabled, On Continuously
3. Default: disabled
Ground Fault Test
This function will test the ground fault trip function of the
controller to ensure proper operation. When selected, the
controller
will
generate
an
artificial
ground
fault
current; if
the ground fault current is sensed as being greater than 30
mA, the test passes. The GF test function will verify actual
ground fault current and heater trip. Status of the test will
be
displayed
as
pass
or
fail.
If
this
test
has
been
invoked
by the “Now” option and it
passes, the user is prompted to reset the ground fault
trip, at which time the load is capa- ble of being re-
energized as required. If this test has been invoked by
the “Autotest” option and it passes, the load is allowed
to be reenergized as required. If this test has been
invoked by the Autotest cycle and it fails, an Autotest
alarm is generated but the load is allowed to be
reenergized as required.
4. Display Mode: Advanced
5. Range:Autotestcycle,Now,Disabled
6. Default: Disabled
1
7
©201
7
Nelson Heat Tracing Systems
www.nelsonheaters.com
GA2497 Rev.
5