INSTALLATION
AXPTC125 POWER TEE SPLICE CONNECTION KIT
INSTRUCTIONS
TULSA, OK 74146
TEL 918-627-5530
FAX 918-641-7336
www.nelsonheaters.com
GA-5052 Rev. 3
Sheet 4 of 10
August 2017
Trim away any frayed or damaged bus wire
ends.
Pull braid tight to form a pigtail.
Lightly score core material and snap off at base
of bus wires.
11
12
HEATING CABLE PREPARATION
Insert guide tubes into power termination fitting, if
required. Note: XLT cable will need to be installed
without the assistance of guide tubes.
Insert buss wires into guide tubes, if used.
Make sure that all buss wire strands are
inserted through fitting tubes.
Remove guide tubes, if used previously.
Squeeze power termination opening and fill
void with silicone adhesive.
Push power termination to overlap jacket.
The silicone will set up in approximately 30
minutes with a complete cure after 24
hours.
Be sure that bus wires do not bunch or cross-over
1
2
3
4
POWER TERMINATION INSTALLATION
WARNING