15 • MultiFlex ESR I&O Manual
026-1720 Rev 4 06-APR-2010
Valve Specifications Tables
Emerson Flow Controls Stepper Valves
Notes:
(1)
500 steps for valves manufactured before year 2001. Identify using date code before 0100 (e.g., 0052, 9902, 9848, or brass body size
~2" vs. ~2
1/4" for 800 steps.
(2)
DO NOT exceed max steps of 384 for this valve.
(3)
Shown for 12V and
24V
motors,
+/- 10% at 75°F.
(4)
For ESV replacement with ESVB: 1. Swap the Flow Control colors RED and BLUE. 2. Cap off the YELLOW wire.
Sporlan (Parker) Stepper Valves
TYPE
ESR 12
ESR 20
ESVB
10-20 Ton
ESVB
(4)
1-4 Ton
ESV
(4)
Voltage
12 VDC
24 VDC
12 VDC
24 VDC
12 VDC
24 VDC
12 VDC
24 VDC
12 VDC
24 VDC
Control
Suction
Suction
Liquid
Liquid
Liquid
Step Rate
50
50
50
50 (30 ok)
30
Max Steps
500/800
(1)
800
800
384
360
(2)
OverClose
5%
5%
5%
5%
5%
Total Watts
10
10
10
3.4
12.8
Phase
(3)
Resistance
29 ohms
115 ohms
29 ohms
115 ohms
29 ohms
116 ohms
84 ohms
336 ohms
23.5 ohms
95 ohms
Hysteresis
0
0
0
0
0
Motor
Bipolar
Bipolar
Bipolar
Bipolar
Unipolar
products
ESR, CC100
CCB
ESR, CC100
CCB
CC100
CCB
CC100
CCB
CC100
CCB
TYPE
CDS-8
CDS-16
CDS-17
SEI/EEV
CDS-9
Voltage
12 VDC
12 VDC
12 VDC
12 VDC
Control
Suction
Suction
Suction
Suction
Step Rate
200
200
200
200
Max Steps
3064
6386
1596
3193/6386
OverClose
5%
10%
10%
10%
Total Watts
10
4
5.7
4
Phase
(3)
Resistance
75 ohms
75 ohms
72 ohms
75 ohms
Hysteresis
0
0
0
0
Motor
Bipolar
Bipolar
Bipolar
Bipolar