Type MR105
5
Figure 3.
Type MR105 with High-Pressure Actuator Operational Schematic
M1181
TyPe y602-12 VeNT PoINTed doWN
oR 1/2 NPT PReSSURe-LoAded
SPRINg CASE VENT
VALVE PLUg
DIAPHRAgM
SEAT RINg
TyPe y602-12 VeNT
CONTROL SPRINg
ACTUATOR
ACTUATOR STEM
CAgE
VALVE SPRINg
1/2 NPT CoNTRoL
LINE CONNECTION
Table 3.
Maximum Inlet, Outlet and Emergency Casing Pressure
(1)
BODY
MATERIAL
END
CONNECTION
MAxIMUM INLET
PRESSURE
MAxIMUM OUTLET PRESSURE
MAxIMUM EMERgENCY CASINg PRESSURE
Low-Pressure
Actuator
High-Pressure
Actuator
(2)
Low-Pressure
Actuator
High-Pressure
Actuator
(2)
psig
bar
psig
bar
psig
bar
psig
bar
psig
bar
Cast Iron
NPT
340
23.4
70
4.8
340
23.4
70
4.8
340
23.4
CL125 FF
175
12.1
175
12.1
175
12.1
CL250 RF
400
27.6
400
27.6
400
27.6
WCC steel
NPT
400
27.6
70
4.8
400
27.6
70
4.8
400
27.6
CL150 RF
245
16.9
245
16.9
245
16.9
CL300 RF
400
27.6
400
27.6
400
27.6
CL600 RF
PN 16 RF
245
16.9
245
16.9
245
16.9
PN 16/25/40 RF
400
27.6
400
27.6
400
27.6
CF8M
Stainless steel
NPT
400
27.6
70
4.8
400
27.6
70
4.8
400
27.6
CL150 RF
225
15.5
225
15.5
225
15.5
CL300 RF
400
27.6
400
27.6
400
27.6
CL600 RF
PN 16 RF
225
15.5
225
15.5
225
15.5
PN 16/25/40 RF
400
27.6
400
27.6
400
27.6
CF3M
Stainless steel
NPT
400
27.6
70
4.8
400
27.6
70
4.8
400
27.6
CL150 RF
185
12.7
185
12.7
185
12.7
CL300 RF
400
27.6
400
27.6
400
27.6
CL600 RF
PN 16 RF
185
12.7
185
12.7
185
12.7
PN 16/25/40 RF
400
27.6
400
27.6
400
27.6
1. Based on a maximum temperature of 250°F / 121°C.
2. Maximum outlet and emergency casing pressures for constructions with Fluorocarbon (FKM) diaphragm are limited to 230 psig / 15.8 bar or the body rating limit, whichever is lower.
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE