43
Reference Manual
24625020, Rev AA
March 2017
4.
To simulate the electrode in water, remove the electrode cover and short the
electrode sense element terminal to ground through a 120 k
resistor (when
configured for High Sensitivity operation) or a 56 k
resistor (when configured for
Low Sensitivity operation).
5.
Check the front panel LED states are as expected:
!
LED off
STEAM
LED off
WATER
LED on
6.
Check the fault and status relays are as expected:
a.
Fault relay energized
b. Status relay de-energized
7.
To check system operation in steam, remove the resistor.
If the Status Relay Operation setting is set to latched, the Control Unit must be
power cycled to set the status relay back to the energized position
8.
Check the front panel LED states are as expected:
!
LED off
STEAM
LED on
WATER
LED off
9.
Check the fault and status relays are as expected:
a.
Fault relay energized
b. Status relay energized
Red
White
120
or 57
Black
Black or blue