3.4  Switch Setting Adjustment 

 
Access to switches is achieved by removing control unit from base, unclipping plastic panel from rear of control unit 
and sliding PCB from housing.  After setting switches, reassemble by reversing the disassembly procedure. 
 

 

 

Figure 3 : 

 

There is one set of four switches on the pcb of the MES*L unit, which is labelled SW1.  This has four colour coded switches 
which can be off to the left (in the diagram above) towards the word OFF on the switch itself, or ON to the right, in the direction 
of the arrow towards the numbers 1, 2, 3 and 4. 
 

4.0  Technical Specifications 

 

Main relay output 

5 amp SPCO resistive 250V a.c. 

Fault relay 

5 amp SPCO resistive 250V a.c. 

Power supply 

110/120v a.c. ± 10% 
220/240v a.c. ± 10% 
50/60 Hz 

Temperature range 

-20°C to + 65°C 

Housing 

IP20 enclosure designed for wall mounting 
with 2 screws.  Optional DIN rail adaptor 
available 

Dimensions : mm 

H = 150 x W = 75 x D = 112 

Mounting holes 

2 x 3mm  Ø  on C/L 100mm apart 

Sensor power (for 1 or 2 separate Mobrey 
Electrosensor) 

12v DC nominal  
Intrinsically safe 

ATEX 

II (1) G [EEx ia] IIC 

LED Indicators 

1 (Green) main relay on 
2 (Yellow) main relay off 
3 (Yellow) fault relay off 
NOTE: Fault relay is energised in normal state, 
de-energised or off in the fault condition 

Max. cable resistance each core 

100 ohms 

Weight 

600 grams 

Maximum altitude 

2000 m 

Maximum humidity 

95% 

 

 
 
 
 
 

Summary of Contents for Mobrey Electrosensor

Page 1: ... CONTENTS 1 0 Safety information 2 1 1 Protection 2 1 2 Explanation of symbols 2 2 0 Application 2 2 1 Technical description 2 3 0 Installation 2 3 1 Wiring 2 3 2 Terminal arrangements 3 3 3 Printed circuit board 3 3 4 Switch setting adjustment 4 4 0 Technical specifications 4 5 0 Model identification 5 6 0 Maintenance Inspection 5 ...

Page 2: ...See instruction manual IP264 for further information The output relay of the MES L is set according to this sensor current and the setting of switch 1 See Fig 3 Fault monitoring is achieved by checking the current drawn is within the band 4mA to 20mA If a fault state exists current outside of band then the fault relay de energises For instructions specific to units used in hazardous area installat...

Page 3: ...ectrical noise 3 2 Terminal arrangements Figure 1 MES L Terminals Connections Notes Relay terminals are shown in the de energised state Terminals 2 3 are linked on the MES L pcb and can use one field cable core if required When two sensors are used with one control unit for a pump control application the sensor on terminals 1 2 must be the top sensor and the lower liquid level sensor must be attac...

Page 4: ...Technical Specifications Main relay output 5 amp SPCO resistive 250V a c Fault relay 5 amp SPCO resistive 250V a c Power supply 110 120v a c 10 220 240v a c 10 50 60 Hz Temperature range 20 C to 65 C Housing IP20 enclosure designed for wall mounting with 2 screws Optional DIN rail adaptor available Dimensions mm H 150 x W 75 x D 112 Mounting holes 2 x 3mm Ø on C L 100mm apart Sensor power for 1 or...

Page 5: ... Code Voltage requirements 1 220 240V ac 50 60 Hz 2 110 120V ac 50 60 Hz Code Output relay S SPCO MES 3 L 1 S 6 0 Maintenance Inspection This is limited to periodic inspection by a qualified person to ensure that the installation including wiring and equipment housing is safe Clean only with a damp cloth ensuring that no moisture enters control unit Check unit for damage and if damaged do not use ...

Page 6: ...Page 6 ...

Page 7: ...Page 7 ...

Page 8: ...3589 mobrey sales EmersonProcess com www mobrey com Mobrey SA NV Belgium tel 02 465 3879 Mobrey GmbH Deutschland tel 0211 99 808 0 Mobrey SA France tel 01 30 17 40 80 Mobrey sp z o o Polska tel 022 871 7865 Mobrey AB Sverige tel 08 725 01 00 2005 Mobrey The right is reserved to amend details given in this publication without notice ABCDEF ...

Reviews: