Figure 3.14 – Typical Lorain CIP distribution section load cabling
3.2.5.2. Electrical specifications of the Lorain CIP distribution
The electrical specifications of the Lorain CIP
distribution section are listed
in the following table (refer also to notes 1 to 12 in section 3.2.5.1):
Table 3.9 – Electrical specifications of the Lorain CIP distribution section
Parameter
Specifications
Internal busbar capacity
charge: 120 A at 55
°
C, 90 A at 65
°
C
discharge: 120 A at 55
°
C, 90 A at 65
°
C
Shunt rating (75 mV drop)
200 A
LVD (optional) capacity
120 A at 60 V dc
LVD operating voltage
nominal:
–48.0 V dc
range:
–42.0 to –50.0 V dc
Number of load protection devices
up to 20 (see details next page)
Capacity range of circuit breakers
1-100 A
Capacity range of TPS fuses
1-50 A
SAN-O fuse rating for 10-position fuse kit AX1: 0.180 A to 10 A (SAN-O)
AX2: 20 A (SAN-O)
GMT fuse rating (optional 8-position fuse
kit)
0.180 A to 15 A (GMT)