REV. 5
7/6/2007
Liebert Monitoring Group –Development
24
Input Phase Rotation
Error
10191
1
1
Bypass Phase Missing
10201
1
1
Bypass Input Voltage
Fail
10202
1
1
Bypass Under Voltage
Fail
10203
1
1
Bypass Under Voltage
Warning
10204
1
1
Bypass Over Voltage
Fail
10205
1
1
Bypass Over Voltage
Warning
10206
1
1
Output Under Voltage
10218
1
1
Output Over Voltage
10219
1
1
Output Short Circuit
10220
1
1
Module with Active
Alarm
10304
1 1
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number Of Input Lines
30004
40004
1
1
Bits 12 - 15
Number Of Bypass
Lines
30004
40004
1
1
Bits 4 - 7
Number Of Output
Lines
30004
40004
1
1
Bits 8 - 11
Number Of Sub-
Modules
30009
40009
1
1
Nominal Power Rating
30021
40021
2
1
VA
Nominal Input Voltage
30027
40027
1
1
V
Nominal Output
Voltage
30028 40028 1
1 V
Nominal Static Bypass
Switch Voltage
30029
40029
1
1
V
Nominal Input Current
30030
40030
1
1
A
Nominal Output
Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
Nominal Battery
Voltage
30034
40034
1
1
V
Load (Apparent
Power)
30102
2 1
VA
Load (Real Power)
30104
2
1
W
Load / Capacity
30106
1
1
%
Output Frequency
30108
1
10
Hz
Bypass Frequency
30109
1
10
Hz
Battery Charge Status
30112
1
1 - 100% Charged
2 - Less than 100% Charged
Battery Voltage
30113
1
1
V
Battery Current
30114
1
1
A
Battery Time
Remaining
30115
1 1
min
Battery Charge
Percentage
30116
1
1
%