REV. 5
7/6/2007
Liebert Monitoring Group –Development
29
Liebert DS
Data points Mapped to Input Status and Coils
Reference Document: ST100I&C PA Parameters and Events, Version 18.0
Data Description
Status
Coil#
#
bit
-
Notes
iCOM
Reference
Sleep on Monday
10001
1
1
U603
Sleep on Tuesday
10002
2
1
U603
Sleep on Wednesday
10003
3
1
U603
Sleep on Thursday
10004
4
1
U603
Sleep on Friday
10005
5
1
U603
Sleep on Saturday
10006
6
1
U603
Sleep on Sunday
10007
7
1
U603
Supply Limit Enable
10008
8
1
S105
Reheat Lockout
10009
9
1
S271
Humidifier Lockout
10010
10
1
S272
Temperature Indication [1]
10011
11
1
U404
Timer Mode Type
10012
12
1
U610
Minimum Chilled Water Temp
Enable
10013
13
1
S128
Std. Sensor Alarms Enable
10019
19
1
U202
Sensor A Alarms Enable
10020
20
1
U207
Compressor Lockout
10021
21
1
S274
VSD Fan speed
10022
22
1
S131
Unit Control
-
25
1
EnvState.
SysCtrl
Reset Alarm
-
26
1
..
EnvState.
AlarmCtrl.1
Acknowledge Alarm
-
27
1
..
EnvState.
AlarmCtrl.2
Reset Total Run Hours Fan
Motor
-
28
1
..
U502
Reset Comp1Run Hour
-
29
1
..
U503
Reset Comp2Run Hour
-
30
1
..
U504
Reset Humidifier Run Hour
-
31
1
..
U510
Reset Dehumidifier Run Hour
-
32
1
..
U511
Reset CW/FC Run Hour
-
33
1
..
U505
Reset E-Heater1RunHour
-
34
1
..
U507
Reset E-heater2RunHour
-
35
1
..
U508
Reset E-heater3 Run Hour
-
36
1
..
U509
Reset HG/HW Run Hour
-
37
1
..
U506
Fan On
10025
-
1
FanSym
Cool On
10026
-
1
CoolSym
Free Cool On
10027
-
1
FCSym
Hot Water On
10028
-
1
HWSym
Electrical Heater On
10029
-
1
HeatSym