UPS Web management by Liebert IS-WEBRT3 Card
11
5.3
Configuration
Sub-Menu
• UPS Configuration
• UPS On/Off Schedule
• Network
• SNMP
• Email
• WEB/Telnet
• System Time
• Language
Please set each parameter correctly, so that Liebert IS-WEBRT3 card operates properly.
5.3.1
UPS Configuration
This page is used to set the UPS configuration. Any incorrect settings will cause incorrect display val-
ues or disconnection between the UPS and Liebert IS-WEBRT3 card.
UPS Properties
UPS Communication Type
—This section is used to set up the communication interface of the UPS.
(e.g., Contact Closure/RS232/3 phase, etc.) Please refer to the UPS manual to set the correct commu-
nication type. Any incorrect settings will cause disconnection between the UPS and Liebert
IS-WEBRT3 card .
UPS Rating Voltage(V)
—This section is used to set the UPS Rating Voltage. (Unit: Volt). Refer to
the UPS manual for details.
Number of Battery
—This is used to set the UPS battery unit number. Please refer to the UPS man-
ual.
Battery Charge Voltage
—This section is used to set the UPS battery Charge Voltage. (Unit: Volt).
Refer to the UPS manual for details.
Last Battery Replaced Date ( mm/dd/yyyy)
—This section is to record the date when the UPS bat-
tery was last replaced.
UPS Recorded
UPS Data Log
—This section is used to set how often the UPS data should be logged.
Test UPS
Test UPS for every
—This section is used to schedule the UPS to test once a week or once every two
weeks.
Test UPS on Weekday
—This section is used to set the UPS to test on a particular day of a week.
Time of UPS Testing ( hh:mm)
—This section is used to set the UPS to test at a certain time on the
test day.
NOTE
This page’s selection will differ according to the different interface of the UPS.