UPS Web management by Liebert IS-WEBRT3 Card

19

5.4.2

Data Log

This page displays a UPS data log. It records UPS Input Voltage/Output Voltage/ Frequency/ Load-

ing/Capacity/ Temperature. It can log up to 500 events. When this limit is reached, the Liebert 

IS-WEBRT3 card will delete the earliest event record and continue logging new events. Logs can be 

saved in CSV format by clicking on 

Save Data Log

.

Date/Time

—This is a record of the Date (mm/dd/yyyy) and Time (hh:mm:ss) that the data was 

recorded. The interval between every log can be set in /Configuration/UPS configuration/UPS 

recorded/UPS data Log/.

Input Voltage

—This section shows records of the UPS Input voltage readings in volts.

Output Voltage

—This section shows records of the UPS Output voltage readings in volts.

Loading

—This section shows records of the UPS Output loading as %.

Capacity

—This section shows records of the UPS battery capacity as %.

Frequency

—This section shows records of the UPS Input Frequency in Hz.

Temp.—This section shows records of the UPS internal temperature in degrees Celsius.

Figure 24

Date log

5.4.3

Save Data Log

This function is to save a copy of the Data Log information (shown on the screen) to a file. 

Figure 25

Save data log

Summary of Contents for Liebert ISWEBRT3

Page 1: ...Site Monitoring For Business Critical Continuity Liebert ISWEBRT3 User Manual ...

Page 2: ......

Page 3: ...ble DeskPro Net Password or Management Protocol 5 4 3 2 Download Firmware 6 4 3 3 Refresh 6 5 0 UPS WEB MANAGEMENT BY LIEBERT IS WEBRT3 CARD 7 5 1 Introduction 7 5 2 Liebert IS WEBRT3 Card UPS Web Interface 7 5 2 1 Information 8 5 2 2 Basic Information 8 5 2 3 Current Status 9 5 2 4 Remote Control 10 5 2 5 Meter Chart 10 5 3 Configuration 11 5 3 1 UPS Configuration 11 5 3 2 UPS On Off Schedule 12 ...

Page 4: ...BRT3 card UPS IP address 7 Figure 9 Liebert IS WEBRT3 card UPS login dialog 7 Figure 10 System status 8 Figure 11 Basic information 9 Figure 12 Current status 9 Figure 13 Remote control 10 Figure 14 Meter Chart 10 Figure 15 UPS configuration 12 Figure 16 UPS On Off schedule 13 Figure 17 Network 14 Figure 18 SNMP 15 Figure 19 E mail 16 Figure 20 WEB Telnet 17 Figure 21 System time setting 17 Figure...

Page 5: ... traps and e mails for event notification Automatically e mails a daily UPS history Matches with shutdown software to protect computer s file saving and shut down safely 1 2 Applications 1 2 1 Liebert IS WEBRT3 Card Web Interface The system administrator can use a Web browser to check the status of all UPSs where a Liebert IS WEBRT3 has been installed The administrator can access a UPS by entering...

Page 6: ...ED Liebert IS WEBRT3 card Liebert Web Card CD including DeskPro Net Utility Configure Liebert Web Card UPS IP address update firmware Liebert IS WEBRT3 card user manual SL 52665 Liebert IS WEBRT3 card MIB Figure 1 Liebert IS WEBRT3 card ...

Page 7: ...n the monitoring computer b Follow the prompts to install the software After complete installation DeskPro Net Utility will appear in Start Programs Figure 2 Liebert IS WEBRT3 installation Figure 3 Installation steps Insert the Liebert IS WEBRT3 card Connect a network cable to the Liebert IS WEBRT3 card Connect the Liebert IS WEBRT3 Card UPS and Network Set up the Liebert IS WEBRT3 Card s IP Addre...

Page 8: ...een set click Apply to login 4 2 Configure the Liebert IS WEBRT3 Card 1 Select the Liebert IS WEBRT3 card from the right side of the screen and click Configure the window in Figure 5 opens 2 If using a static IP address set the card s IP address subnet mask and gateway See your network administrator for the settings 3 After making the settings open a Web browser such as Microsoft s Internet Explor...

Page 9: ...eference any related param eter setting for the manager Concerning security the manager could use any advanced port setting with the above two methods Followings are the descriptions 1 At advanced setting two functions were set as activated by using port number 80 and 23 2 If the boxes are unchecked the functions will not be available 3 When set to the other port value the full IP address must be ...

Page 10: ...ill reboot automatically Figure 7 Update Liebert IS WEBRT3 card firmware 4 3 3 Refresh Liebert DeskPro Net Utility automatically searches the network for new cards and obtains new data from cards already configured The Refresh function manually prompts the software to search the network for new Liebert IS WEBRT3 cards and obtain new data NOTE The Liebert IS WEBRT3 card protects against interruptio...

Page 11: ... 67 51 in the example in Figure 8 Figure 8 Input Liebert IS WEBRT3 card UPS IP address 3 When prompted enter the password If no password has been set press the Enter key or click OK Figure 9 Liebert IS WEBRT3 card UPS login dialog Fig 5 2 Liebert IS WEBRT3 Card UPS Web Interface Enter the Liebert IS WEBRT3 card s Web interface There are four main function items in the first Web page Information Co...

Page 12: ...ebert IS WEBRT3 card Other values are user settings from the Configuration pages Network Status This section shows the Liebert IS WEBRT3 card Network settings The MAC address is provided by the Liebert IS WEBRT3 card All other values in this section are user settings from the Configuration pages Figure 10 System status 5 2 2 Basic Information This page show the UPS basic information Values here ar...

Page 13: ...ows the UPS input status including AC Status Input Voltage Input Frequency Values here will be shown in red when an abnormal status condition occurs Output Status This section shows the UPS output status including Output Voltage Output Status UPS Loading Values here will be shown in red when an abnormal status condition occurs Battery Status This section shows the UPS Battery Status including Temp...

Page 14: ...n AC Failed Cancel Test This function aborts a test when it is executing Turn Off UPS When AC Failed Reboot UPS Selecting Turn off UPS when AC failed will turn off the UPS You can reboot the UPS by selecting Reboot UPS Put UPS in Sleep mode for __ minutes Wake up UPS When the UPS is put into Sleep mode it will not provide power The UPS will provide power after exiting Sleep mode Figure 13 Remote c...

Page 15: ...UPS Rating Voltage V This section is used to set the UPS Rating Voltage Unit Volt Refer to the UPS manual for details Number of Battery This is used to set the UPS battery unit number Please refer to the UPS man ual Battery Charge Voltage This section is used to set the UPS battery Charge Voltage Unit Volt Refer to the UPS manual for details Last Battery Replaced Date mm dd yyyy This section is to...

Page 16: ...rnal temperature Lie bert IS WEBRT3 card will send warning messages when the UPS overheats Figure 15 UPS configuration 5 3 2 UPS On Off Schedule This page is used to schedule On Off time for the UPS This page is used to schedule the UPS for automatic start and shutdown Weekly Schedule This section is to set the time to turn the UPS On Off each day of the week Date Schedule This section is to set t...

Page 17: ...a DHCP The four sections above can be set in Liebert DeskPro Net as well The Liebert IS WEBRT3 card will reboot after any of the above are changed DNS Server IP Primary DNS Server IP This section is used to set the Liebert IS WEBRT3 card primary DNS Server IP address Secondary DNS Server IP This section is used to set the Liebert IS WEBRT3 card secondary DNS Server IP address The Liebert IS WEBRT3...

Page 18: ...set options for administrators Options are Read Read Write and No Access Description This section is available for an administrator to make notes Trap Notification Receiver IP Address This section is used to set the receivers IP address for traps sent by the Lie bert IS WEBRT3 card It is valid for up to eight IP addresses Community This section is used to set a Community name for an NMS The commun...

Page 19: ...e mail account name when the email server requires authentication Password This section is used to set a password when the e mail server requires authentication Send Email When Event Occurs This section is used to set the Liebert IS WEBRT3 card to send warning e mail when an event occurs Recipient s Email Address for Event Log This section is used to designate e mail addresses to receive warning e...

Page 20: ...d User Name This section is used to set a user name for the Liebert IS WEBRT3 card Web pages It is valid for up to eight users Users must enter the user name to access the Liebert IS WEBRT3 card Web pages from a Web browser Password This section is used to set a password for the Liebert IS WEBRT3 card Web pages Users must enter the password to access the Liebert IS WEBRT3 card Web pages from a bro...

Page 21: ...his section is used to set an interval for time synchroniza tion Primary Time Server Secondary Time Server This section is used to set a Primary Time Server and a Secondary Time Server for the Liebert IS WEBRT3 card Time Zone Relative to GMT This section is used to set a different time zone for different coun tries System Time mm dd yyyy hh mm ss This section is used to set the Liebert IS WEBRT3 c...

Page 22: ... mail sent by the Liebert IS WEBRT3 card Figure 22 Language 5 4 Log Information Sub Menu Event Log Data Log Save Data Log 5 4 1 Event Log This page displays a UPS Event log It shows a record of all events giving the Date Time of the event and a detailed description of each It can log up to 99 events When this limit is reached Liebert IS WEBRT3 card will delete the earliest event record and continu...

Page 23: ...val between every log can be set in Configuration UPS configuration UPS recorded UPS data Log Input Voltage This section shows records of the UPS Input voltage readings in volts Output Voltage This section shows records of the UPS Output voltage readings in volts Loading This section shows records of the UPS Output loading as Capacity This section shows records of the UPS battery capacity as Frequ...

Page 24: ...ent configuration Click Save to save the configuration as a text file The text file will have a default format of YYYY_MMDD_ cfg Administrative permission is required Restore previous configuration Use this function to restore a cfg configuration that has been saved earlier Click Browse to the location of the file and click Restore Reset to factory default This function will reset all settings to ...

Page 25: ...6 2 Telnet Configuration 1 Click on Start Run and enter telnet and the Liebert IS WEBRT3 cards IP address Figure 27 Telnet startup 2 If the connection is successful the window in Figure 28 will be displayed Figure 28 Telnet connection 3 Press the Enter key to enter telnet main screen If the user name and password were set previously enter those actual values to gain access 4 If the connection is s...

Page 26: ...Replacement Date Set UPS Devices Connected This section allows setting up the connected devices name rat ing and whether the device is connected Set System Time Time Server This allows setting up the System date time and two time servers Set Web and Telnet User Account This is allows setting up the user accounts authority Set E mail This is allows setting up the e mail accounts to receive power ev...

Page 27: ......

Page 28: ...red to are trademarks or registered trademarks of their respective owners Technical Support Service Web Site www liebert com Monitoring 800 222 5877 Liebert monitoring emerson com Outside the US 614 841 6755 Single Phase UPS 800 222 5877 upstech emersonnetworkpower com Outside the US 614 841 6755 Three Phase UPS 800 543 2378 powertech emersonnetworkpower com Environmental Systems 800 543 2778 Outs...

Reviews: