22
15: Charger maximum current setting
Interface
Setting
Parameter 2:
The maximum charging current could be
adjusted.
Default value is 4A for long run model and 1A for standard
model. The setting range is 0.5A~6A for long run model, and
0.5A~2A for standard model
Note:
Any modification should be suitable to battery specifications.
If input voltage is below 200VAC, the UPS will reduce charging
current to 4A automatically even though the setting is 6A.
16: Battery capacity setting
Interface
Setting
Parameter 2:
Set the battery capacity such as 7AH, 9AH, 10AH,
12AH, 17AH, 26AH, 40AH, 65AH, 100AH and so on.
The default value is 9AH.
17: Battery groups setting
Interface
Setting
Parameter 2:
Set battery group range from 1 to 6.
The default value is 1 group.
These parameters are for the battery backup time calculation
18: Backup time calibration
Interface
Setting
Parameter 2:
Calibrate the displayed backup time by adjusting
this multiplier factor. The displayed backup time will be equal
with the original calculated backup time multiply this value.
The default value is 1.0, and the range is from 0.5 to 2