Installation Drawings
147
Figure 155 Raised floor mounting
2"
(50mm) dia.
1/2" (12.7mm)
dia. steel bolt
Large diameter washer
Lockwasher
Raised
floor
F
NOTE: Combination of floor material of given thickness , plus
properties of large diameter washer and fastener , should result in
lateral load capability to withstand shear due to load F =1500 lb (680kg),
parallel to floor .
For thicker floors that might require a bolt length longer than
can fit inside mounting channel , insert bolt from below with nut above .
F
F
F
29-½” (75mm)
16” (406mm)
TOP VIEW