Liebert iCOM
®
Control
Liebert
®
CRV
™
96
11.3.3 Fan Speed
The heating control is active only when the unit is in dehumidification mode. The reheats will begin
activation when the control temperature has dropped to -66% of the control’s proportional band and
will deactivate when the temperature setpoint has been reached. The heating proportional band is
established using the following formula and control lines:
S102 Temperature Se (1/2 * S105 Temperature Deadband) + S108 Heating Proportional Band = heating
control band.
S109 Heating integration time works with the heating control band to stage reheat and maintain
tight temperature control. The items that make up the heating control band can be viewed and
adjusted in the Service menus, Setpoints.
Figure 68 Service Menu Setpoint screen for Fan Speed
11.3.4 Air Flow
The Liebert CRV's airflow can be controlled manually or dynamically by temperature sensors.
Manual Fan Control:
Cooling off supply, remote, or return sensor are permitted in manual fan
speed control. Manual control of the Liebert CRV’s fan speed can be achieve in two ways:
• Manually setting the fixed speed at the local display OR
• Remote monitoring
To control the fan manually using either method, locate Service menus, Setpoints, line S124 Fan
Control Type. The factory default is
Auto
with an alternative selection of
Manual
. S124 must be set
as
Manual
before a manual fan setpoint point can be programmed. With the fan control type set for
Manual
, the fan speed may be set from 50% to 100% at the local display using S130 Fan Speed
Manual Setpoint. A Liebert IntelliSlot
®
card or other Liebert site monitoring integration is required
for remote fan control.Visit
for more information about Liebert monitoring
products. A list of monitoring points is available in document SL-28170 (Liebert IntelliSlot
®
Modbus
485, Modbus IP and BACnet IP). This document can also be obtained by visiting
Figure 69 Service Menu Setpoint screen for Airflow