Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor
44
5.4.1 Expansion Tanks, Fluid Relief Valves and Other Devices
An expansion tank must be provided for expansion and contraction of the fluid due to temperature
change in this closed system. Vents are required at system high points to vent trapped air when fill-
ing the system. A relief valve is a also a necessary piping component.
Depending on the complexity of the system, various other devices may be specified. Pressure gauges,
flow switches, automatic air separator, tempering valves, standby pumps, sensors for electrical con-
trols, and flow switches are just a few of these devices.
NOTICE
Risk of freezing temperatures. Can cause equipment and piping damage.
Immediately following the use of water for leak testing or system cleaning, charge the tested
system with the proper percentage of glycol and water for your coldest design ambient.
Complete system drain-down cannot be assured and damage to the system could result from
freezing of residual water.
5.5
Filling Instructions
5.5.1 Preparing the System for Filling
It is important to remove any dirt, oil or metal filings that may contaminate the cooling system piping
in order to prevent contamination of the fresh glycol solution and fouling of the drycooler piping. The
system should be flushed thoroughly using a mild cleaning solution or high-quality water and then
completely drained before charging with glycol. Cleaning new systems is just as important as clean-
ing old ones. New systems can be coated with oil or a protective film; dirt and scale are also common.
Any residual contaminants could adversely affect the heat transfer stability and performance of your
system. In many cases, in both old and new systems, special cleaners are needed to remove scale, rust
and hydrocarbon foulants from pipes, manifolds and passages. Clean heat transfer surfaces are
important in maintaining the integrity of the heating/cooling system. For more information on clean-
ers and degreasers, contact your sales representative. Follow the manufacturer's instructions when
using these products.
Calculate the internal volume of the system as closely as possible. See
Table 14
and
Table 16
for
unit volumes. Use volume in
Table 15
for glycol piping volumes.
Table 14
Indoor unit glycol volume approximate gallons (liters) max.
Model (50 Hz)
Glycol-Cooled
GLYCOOL
046WG/(045WG) 1.2
(4.5)
—
071WG/(070WG) 2.0
(7.5)
—
061G/(058G) —
4.0
(15.1)
Table 15
Volume in standard Type “L” copper piping
Diameter (in.)
Volume
Outside
Inside
Gal/Ft
L/M
1/2 0.123
0.008
0.01
5/8 0.555
0.012
0.15
3/4 0.666
0.018
0.22
7/8 0.785
0.025
0.31
1-1/8 1.025
0.043
0.53