Installation, Operation and Maintenance Manual
VCIOM-02377-EN Rev. 0
May 2022
13
Section 6: DeviceNet Interface Module
DeviceNet Interface Module
Net_Stat
•
Network Status LED as defined in spec. Vol. 3, “DeviceNet Adaptation for CIP”,
Section 7
Table 2.
Reset
•
Reset pushbutton
Local Configuration
•
On-board interface for local configuration of MACID and Baud Rate. By default,
the board is set to accept MACID and Baud Rate from the network, but it is also
possible to set these parameters by hardware setting. Detailed procedures are
given in Section 9, Local Settings.
Condition
LED
Description
Not powered/not on-line
Off
Device is not on-line
On-line, not connected
Flashing green
Device is on-line, but is not allocated to
a Master
Link OK on-line connected Green
Device is on-line and is not allocated to
a Master
Connection time-out
Flashing red
One or more I/O connection are in
timed-out state
Critical link failure
Red
Failed communication device. The device
has detected an error that has rendered it
incapable of communicating on the network
(Duplicate MACID or Bus-Off).
Communication faulted
and received an identify
comm fault
request-long protocol
Flashing red and green
A specific communication faulted device.
The device has detected a Network Access
error and is in the Communication Faulted
state. The device has subsequently received
and accepted an Identify Communication
Faulted Request-Long Protocol message.